Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2015, 11:32 AM
  • 22 0751_22 0750_20151204_035525.mp4

Date
12/04/2015
W/O
536652
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00821
PipeID
P17108
Time
3:32 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2878
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
SAN DIMAS, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
V
Project
WO_536652_TV22057_NOV2015
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0750
Downstream MH
22 0751
Dir. of Survey
Upstream
Length Surveyed
262.2 ft.
Total Length
262.2 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
2
O&M Quick
3122
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
163
Pipe schematic from manhole 22 0750 to 22 0751
MH: 22 0750MH: 22 0751upstream0 ft. MSA - Survey Abandoned - REVERSAL COMPLETE0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0.1 ft. MGO - General Observation - REVERSAL COMPLETE2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish7.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"59 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"104.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"209.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"212.9 ft. RMJ - Roots Medium Joint, from 01 to 05 o'clock, 25 %, within 8 inches of joint: YESR253.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"258.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start260.2 ft. MGO - General Observation - MAGNESIUM H.O. START 80%262.2 ft. MGO - Reversal Inspection262.2 ft. MWM - Water Mark, 45 %of cross sectional area262.2 ft. MWL - Water Level, 15 %of cross sectional area262.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 2262.2 ft. AMH - Downstream Manhole, Survey Begins - 22 0750

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 2

    0 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 2

Observations (18)

DistanceCodeObservation
254.3TFC
0MGO
53.1TFC
8.9TFC
0MWM
0MWL
262.2MSAREVERSAL COMPLETE
203.2TFC
2MGOMAGNESIUM H.O. START 80%
262.2DAGS
260SAV
3.5DAGS
0SAV2
262.1MGOREVERSAL COMPLETE
0AMH22 0750
49.3RMJ
157.7TFC
105.7TFC

Properties (5)

additional_info
SC205646
custom_field_two
0
customer
LACSD
datetime
2015-12-04T03:32:51-08:00
sewer_category
SIPHON