Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2015, 11:17 AM
  • 22 0750_22 0749_20151204_033232.mp4

Date
12/04/2015
W/O
536652
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00821
PipeID
P17107
Time
3:17 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2878
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
SAN DIMAS, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Routine Assessment
Project
WO_536652_TV22057_NOV2015
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0749
Downstream MH
22 0750
Dir. of Survey
Upstream
Length Surveyed
349 ft.
Total Length
349 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
207
O&M Index
2
O&M Quick
2212
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
213
Pipe schematic from manhole 22 0749 to 22 0750
MH: 22 0749MH: 22 0750upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 07501.3 ft. MGO - General Observation - MAGNESIUM H.O. FINISH2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish22 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"99.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"191.3 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish196 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"248.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"269.3 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start299.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"340.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"345.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start347 ft. MGO - General Observation - MAGNESIUM H.O. START 80%347 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start349 ft. MWM - Water Mark, 35 %of cross sectional area349 ft. AMH - Downstream Manhole, Survey Begins - 22 0749349 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
0MWM
0AMH22 0749
153TFC
100.9TFC
2MGOMAGNESIUM H.O. START 80%
347.7MGOMAGNESIUM H.O. FINISH
2SAV
347SAV
249.7TFC
327TFC
346.6DAGS
0MWL
3.2DAGS
8.6TFA
157.7RFJ
201.1TFC
49.4TFC
349AMH22 0750
79.7RFJ

Properties (5)

additional_info
SC205646
custom_field_two
3
customer
LACSD
datetime
2015-12-04T03:17:00-08:00
sewer_category