Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 25, 2015, 10:42 AM
  • 14 0219_14 0218A_25112015_024313.mp4

Date
11/25/2015
W/O
536453
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00575
PipeID
P18265
Time
2:42 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2871
Sewer Name
14 NORTH SIDE TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
03
Purpose
Routine Assessment
Project
WO_536453_TV14067_NOV2015
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
14 0219
Downstream MH
14 0218A
Dir. of Survey
Downstream
Length Surveyed
275 ft.
Total Length
275 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
45
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
2
Overall Quick
Overall Rating
161
Pipe schematic from manhole 14 0219 to 14 0218A
MH: 14 0219MH: 14 0218Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 02190 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area7.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start42.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"47.4 ft. TBB - Tap Break-In Abandoned, at 02 o'clock, -, within 8 inches of joint: YES, 6"54.8 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"99.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"103.4 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"111.1 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"156.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"160.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"171.8 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"194.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES202.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start218.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"222.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"233.1 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"271.1 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"271.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish271.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish273.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK275 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK275 ft. AMH - Downstream Manhole, Survey Ends - 14 0218A

Observations (25)

DistanceCodeObservation
0AMH14 0219
275MGOCONNECTION AT THE MH 9 O'CLOCK
47.4TBB
218.3TBA
0MWM
233.1TBC
42.3TBA
273.8MGOCONNECTION AT THE MH 3 O'CLOCK
202.8CM
7.2DAGS
271.1TBC
171.8TBC
194.4CM
99.9TBA
0MGOCONNECTION AT THE MH 3 O'CLOCK
222.1TBA
271.1DAGS
54.8TBC
160.1TBA
271.1CM
156.9TBA
0MWL
111.1TBC
103.4TBA
275AMH14 0218A

Properties (5)

additional_info
SC205639
custom_field_two
4
customer
LACSD
datetime
2015-11-25T02:42:17-08:00
sewer_category
GRAVITY