Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 22, 2015, 07:05 AM
  • H 1253_H 1252_20151221_230945.mp4

Date
12/21/2015
W/O
536444
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01181
PipeID
P17178
Time
11:05 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2896
Sewer Name
H JOINT OUTFALL H - UNIT 8K
City
COVINA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
25
Purpose
Routine Assessment
Project
WO_536444_TV22032_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
H 1253
Downstream MH
H 1252
Dir. of Survey
Downstream
Length Surveyed
85.8 ft.
Total Length
85.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
1
Overall Quick
Overall Rating
2
Pipe schematic from manhole H 1253 to H 1252
MH: H 1253MH: H 1252downstream0 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - H 12532 ft. MGO - General Observation - BEGIN MAGNESIUM HYDROXIDE COATING85.7 ft. VC - Vermin Cockroach85.7 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK85.8 ft. AMH - Downstream Manhole, Survey Ends - H 1253

Observations (9)

DistanceCodeObservation
0VC
85.7VC
0MWL
85.7MGOCONNECTION AT MANHOLE ACTIVE 3 O'CLOCK
0MWM
0MGOCONNECTION AT MANHOLE ACTIVE 9 O'CLOCK
0AMHH 1253
85.8AMHH 1253
2MGOBEGIN MAGNESIUM HYDROXIDE COATING

Properties (5)

additional_info
SC224474
custom_field_two
4
customer
LACSD
datetime
2015-12-21T23:05:00-08:00
sewer_category
GRAVITY