Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 24, 2015, 09:48 AM
  • H 1264_H 1263_20151224_020123.mp4

Date
12/24/2015
W/O
536444
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01181
PipeID
P17189
Time
1:48 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2898
Sewer Name
H JOINT OUTFALL H - UNIT 8K
City
WEST COVINA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
WO_536444_TV22032_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
H 1264
Downstream MH
H 1263
Dir. of Survey
Downstream
Length Surveyed
346.3 ft.
Total Length
346.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
1
Overall Quick
Overall Rating
1
Pipe schematic from manhole H 1264 to H 1263
MH: H 1264MH: H 1263downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 12640 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. MGO - General Observation - BEGIN MAGNESIUM HYDROXIDE COATING11.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"18.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"25.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"62.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"102.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"110.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"182.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"219.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"229.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"279.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"345.2 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK345.2 ft. VC - Vermin Cockroach346.3 ft. AMH - Downstream Manhole, Survey Ends - H 1263

Observations (17)

DistanceCodeObservation
346.3AMHH 1263
62.7TFA
2MGOBEGIN MAGNESIUM HYDROXIDE COATING
102.2TFA
11.3TFA
219.2TFA
0MWL
345.2MGOCONNECTION AT MANHOLE ACTIVE 3 O'CLOCK
110.1TFA
0AMHH 1264
279.6TFA
0MWM
18.3TFA
25.9TFA
229.2TFA
345.2VC
182.9TFA

Properties (5)

additional_info
SC224476
custom_field_two
4
customer
LACSD
datetime
2015-12-24T01:48:00-08:00
sewer_category