Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 24, 2015, 11:03 AM
  • H 1235_H 1234_20151224_032057.mp4

Date
12/24/2015
W/O
536444
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01181
PipeID
P17160
Time
3:03 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2898
Sewer Name
H JOINT OUTFALL H - UNIT 8K
City
WEST COVINA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
24
Purpose
Routine Assessment
Project
WO_536444_TV22032_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
H 1235
Downstream MH
H 1234
Dir. of Survey
Downstream
Length Surveyed
390.8 ft.
Total Length
390.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4131
O&M Rating
161
Overall Index
2
Overall Quick
Overall Rating
161
Pipe schematic from manhole H 1235 to H 1234
MH: H 1235MH: H 1234downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 12350 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - BEGIN MAGNESIUM HYDROXIDE COATING7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start15 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"23.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"87.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"87.6 ft. RML - Roots Medium Lateral, from 02 to 04 o'clock, 10 %, within 8 inches of joint: YES112.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"119.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"184.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"224.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"231.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6", 6"296.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"344.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"352.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"387.6 ft. MGO - General Observation - END MAG390.8 ft. AMH - Downstream Manhole, Survey Ends - H 1234390.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (1)

  • Roots Medium Lateral, from 02 to 04 o'clock, 10 %, within 8 inches of joint: YES

    87.6 ft. - Roots Medium Lateral, from 02 to 04 o'clock, 10 %, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
0MWM
7DAGS
387.6MGOEND MAG
119.5TFC
344.6TFC
352.7TFC
15TFC
168.4TFC
112.2TFC
390.8AMHH 1234
0AMHH 1235
2MGOBEGIN MAGNESIUM HYDROXIDE COATING
23.6TFC
296.5TFA
87.6RML
390.8DAGS
231.9TFA
184.3TFC
0MGOCONNECTION AT MANHOLE ACTIVE 3 O'CLOCK
224.3TFC
87.4TFA
0MWL

Properties (5)

additional_info
SC224476
custom_field_two
4
customer
LACSD
datetime
2015-12-24T03:03:00-08:00
sewer_category