Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 23, 2015, 07:33 AM
  • H 1276_H 1275_20151222_234714.mp4

Date
12/22/2015
W/O
536444
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01181
PipeID
P17201
Time
11:33 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2897
Sewer Name
H JOINT OUTFALL H - UNIT 8K
City
COVINA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
WO_536444_TV22032_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
H 1276
Downstream MH
H 1275
Dir. of Survey
Downstream
Length Surveyed
174.9 ft.
Total Length
174.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2F00
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
66
Pipe schematic from manhole H 1276 to H 1275
MH: H 1276MH: H 1275downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 12760 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK2 ft. MGO - General Observation - BEGIN MAGNESIUM HYDROXIDE COATING7.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"32.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"72.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"97 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"129 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"161.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"172.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish174.9 ft. AMH - Downstream Manhole, Survey Ends - H 1275

Observations (14)

DistanceCodeObservation
161.5TFA
0AMHH 1276
72.7TFA
172.7DAGS
9.1TFC
7.1DAGS
0MWL
2MGOBEGIN MAGNESIUM HYDROXIDE COATING
0MWM
97TFA
174.9AMHH 1275
0MGOCONNECTION AT MANHOLE ACTIVE 3 O'CLOCK
129TFA
32.7TFA

Properties (5)

additional_info
SC224475
custom_field_two
4
customer
LACSD
datetime
2015-12-22T23:33:08-08:00
sewer_category