Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 24, 2015, 08:52 AM
  • H 1267_H 1266_20151224_011103.mp4

Date
12/24/2015
W/O
536444
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01181
PipeID
P17192
Time
12:52 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2898
Sewer Name
H JOINT OUTFALL H - UNIT 8K
City
WEST COVINA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
WO_536444_TV22032_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
H 1267
Downstream MH
H 1266
Dir. of Survey
Downstream
Length Surveyed
360.2 ft.
Total Length
360.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
140
Pipe schematic from manhole H 1267 to H 1266
MH: H 1267MH: H 1266downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 12672 ft. MGO - General Observation - BEGIN MAGNESIUM HYDROXIDE COATING7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"18.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"41.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"72.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"104 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"111.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"160.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"184.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"207.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"232.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"280.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"288.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"312.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"319.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"357.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish360.2 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK360.2 ft. AMH - Downstream Manhole, Survey Ends - H 1266

Observations (22)

DistanceCodeObservation
184.3TFA
360.2MGOCONNECTION AT MANHOLE ACTIVE 3 O'CLOCK
111.5TFA
7DAGS
288.4TFA
357.6DAGS
280.4TFA
319.7TFA
41.5TFA
104TFA
360.2AMHH 1266
312.3TFA
2MGOBEGIN MAGNESIUM HYDROXIDE COATING
72.6TFA
160.5TFA
0MWM
0MWL
207.9TFA
0AMHH 1267
10.2TFA
232.6TFA
18.2TFA

Properties (5)

additional_info
SC224476
custom_field_two
4
customer
LACSD
datetime
2015-12-24T00:52:00-08:00
sewer_category
GRAVITY