Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2016, 12:33 PM
  • 05 0344_05 0343_11012016_043359.mp4

Date
01/11/2016
W/O
536429
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00432
PipeID
P05558
Time
4:33 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3069
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
WO_536429_TV05014_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
05 0344
Downstream MH
05 0343
Dir. of Survey
Downstream
Length Surveyed
495.5 ft.
Total Length
495.5 ft.
Structural Index
3
Structural Quick
5S3S
Structural Rating
924
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
928
Pipe schematic from manhole 05 0344 to 05 0343
MH: 05 0344MH: 05 0343downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 03442 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start143.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start493.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish493.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish493.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish495.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0343

Observation photos (3)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    143.7 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
493.7SRV
2SRV
493.7SSS
495.5AMH05 0343
0MWM
143.7SSS
0MWL
493.7SAP
2SAP
0AMH05 0344

Properties (4)

additional_info
SC224841
custom_field_two
2
customer
LACSD
datetime
2016-01-11T04:33:37-08:00