Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2016, 12:13 PM
  • 22 0093_22 0092_20160104_043028.mp4

Date
01/04/2016
W/O
531047
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00805
PipeID
P16334
Time
4:13 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2947
Sewer Name
22 DISTRICT #22 MAIN TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
32
Purpose
Routine Assessment
Project
WO_531047_TV22092_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
22 0093
Downstream MH
22 0092
Dir. of Survey
Downstream
Length Surveyed
333.5 ft.
Total Length
333.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4121
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 22 0093 to 22 0092
MH: 22 0093MH: 22 0092downstream0 ft. VC - Vermin Cockroach0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK ACTIVE0 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 22 00930 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - MAGNEZIUM H.O. 50% START53.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 4"61.4 ft. TFI - Tap Factory Made Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 4", 1"109.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"141.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"149.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"189.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"206.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"230.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"254.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"286.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"302.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"330.7 ft. MGO - General Observation - MAGNEZIUM H.O. 50% FINISH333.4 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK ACTIVE333.5 ft. AMH - Downstream Manhole, Survey Ends - 22 0092333.5 ft. VC - Vermin Cockroach

Observation photos (1)

  • General Observation - MAGNEZIUM H.O. 50% START

    2 ft. - General Observation - MAGNEZIUM H.O. 50% START

Observations (22)

DistanceCodeObservation
149.5TFC
141.7TFC
206.6TFC
61.4TFI
302.8TFA
189.8TFC
0VC
333.5AMH22 0092
254.6TFC
230.3TFC
0MWM
286.5TFA
109.2TFC
0MGOLATERAL AT MH 9 OCLOCK ACTIVE
333.4MGOLATERAL AT MH 3 OCLOCK ACTIVE
330.7MGOMAGNEZIUM H.O. 50% FINISH
0MGOLATERAL AT MH 3 OCLOCK ACTIVE
333.5VC
53.2TFA
0AMH22 0093
0MWL
2MGOMAGNEZIUM H.O. 50% START

Properties (5)

additional_info
SC224958
custom_field_two
4
customer
LACSD
datetime
2016-01-04T04:13:41-08:00
sewer_category
GRAVITY