01 0127_01 0126_20160122_035743.mp4
0 ft. - Water Mark, 60 %of cross sectional area
0 ft. - Reversal Inspection

7.1 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

21.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

27.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

46.1 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

157.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - WANDERING
222.1 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish
222.4 ft. - Survey Abandoned - REVERSE INSPECTION COMPLETE
| Distance | Code | Observation |
|---|---|---|
| 0 | MWM | — |
| 157.8 | CM | WANDERING |
| 46.1 | CM | — |
| 222.1 | DAGS | — |
| 27.3 | CL | — |
| 222.1 | MGO | MAGNEZIUM H.O. FINISH |
| 2 | MGO | MAGNEZIUM H.O. START |
| 222.4 | MSA | REVERSE INSPECTION COMPLETE |
| 0 | AMH | 01 0126 |
| 7.1 | DAGS | — |
| 21.7 | CL | — |
| 222.1 | CM | — |
| 222.1 | CM | — |
| 0 | MGO | — |
| 0 | MWL | — |