Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 17, 2017, 10:59 AM
  • 21 0995_21 0994_4172017_043431.mp4

Date
04/17/2017
W/O
0624545
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00784
PipeID
P16095
Time
3:59 AM
Certificate
U-101406022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0496
Sewer Name
21 SAN ANTONIO TRUNK
City
CLAREMONT
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
03
Purpose
Capital Improvement Program Assesment
Project
20170417MDM_SAN_ANTIONIO_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
21 0995
Downstream MH
21 0994
Dir. of Survey
Downstream
Length Surveyed
332.3 ft.
Total Length
332.3 ft.
Structural Index
2
Structural Quick
5141
Structural Rating
84
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
84
Pipe schematic from manhole 21 0995 to 21 0994
MH: 21 0995MH: 21 0994downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:30AM0 ft. MWM - Water Mark, 30 %of cross sectional area7.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT12.1 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL15.5 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE15.5 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT21.6 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL21.6 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL30.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H33.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL37.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H39.8 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL43.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL43.1 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL52.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL54.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H56.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open59 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL68 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL68 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL68.3 ft. MWM - Water Mark, 40 %of cross sectional area77.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL82.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active87.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H89.9 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H94.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H96.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL99.1 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL102.5 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - H102.5 ft. MWM - Water Mark, 30 %of cross sectional area102.5 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H115 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL118.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL124 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT125.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open127.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H133.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL136.7 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL143 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS143 ft. FL - Fracture Longitudinal, at 08TO 4o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS143 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS143 ft. FL - Fracture Longitudinal, at 08 o' TO 4clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS215.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped232.3 ft. MGO - General Observation - 15" VCP247.9 ft. B - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT331.9 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE 30% AT JOINTS331.9 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SLIGHT 60% AT JOINTS331.9 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - SLIGHT 30% AT JOINTS331.9 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE 60% AT JOINTS332.3 ft. AMH - Downstream Manhole, Survey Ends - 5:15AM

Observation photos (2)

  • General Observation - 15" VCP

    232.3 ft. - General Observation - 15" VCP

  • Broken, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    247.9 ft. - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

Observations (53)

DistanceCodeObservation
115FCSL
7.5TFCCapped
82.5TFActive
52.2FMSL
143FCHAIRLINE AT JOINTS
102.5FCH
9FCSLIGHT
43.1FCSL
143FLHAIRLINE AT JOINTS
21.6FCSL
127.4FLH
68.3MWM
102.5MWM
136.7FCSL
68FCSL
331.9FLHAIRLINE 30% AT JOINTS
232.3MGO15" VCP
54.4FCH
118.2FCSL
59FCSL
12.1FCSL
96.4FCSL
30.8FCH
94.1FLH
77.2FCSL
33.7FCSL
331.9FCSLIGHT 60% AT JOINTS
332.3AMH5:15AM
0MWL
143FCSLIGHT AT JOINTS
15.5FCHAIRLINE
102.5FCH
331.9FLSLIGHT 30% AT JOINTS
143FLSLIGHT AT JOINTS
56.6TFOpen
9FCSLIGHT
89.9FCH
331.9FCHAIRLINE 60% AT JOINTS
247.9BSLIGHT
87.3FLH
0AMH4:30AM
43.1FCSL
215.4TFCCapped
68FCSL
124FCSLIGHT
37.1FCH
133.3FCSL
99.1FCSL
39.8FCSL
15.5FCSLIGHT
0MWM
125.3TFOpen
21.6FCSL

Properties (4)

custom_field_three
BROKEN PIPE SLIGHT FRACTURES
custom_field_two
2
customer
LACSD
datetime
2017-04-17T03:59:44-07:00