Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2017, 08:06 AM
  • A 0512_A 0511_462017_012847.mp4

Date
04/06/2017
W/O
0619134
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00315
PipeID
P07748
Time
1:06 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0484
Sewer Name
A JOA-1A DISTRICT 5 INTERCEPTOR
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20170405MDM_JOA_1A_DISTRICT_5_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Upstream MH
A 0512
Downstream MH
A 0511
Dir. of Survey
Downstream
Length Surveyed
653.9 ft.
Total Length
653.9 ft.
Structural Index
4
Structural Quick
5636
Structural Rating
48
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
48
Pipe schematic from manhole A 0512 to A 0511
MH: A 0512MH: A 0511downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:20AM0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 98% 9:00 TO 3:008 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR41 ft. SAP - Surface Aggregate Projecting, from 02 to 03 o'clock, within 8 inches of joint: NO - SEBVERE AGG UNDER MAG COAT89.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGGUNDER MAG COAT99.6 ft. SAP - Surface Aggregate Projecting, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG115.1 ft. SAP - Surface Aggregate Projecting, from 09 to 10 o'clock, within 8 inches of joint: YES - SEVERE AGG131 ft. SAP - Surface Aggregate Projecting, at 01 o'clock, within 8 inches of joint: NO - SEVERE AGG161.7 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR242.9 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR518 ft. SAP - Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG567.3 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR647.4 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR650 ft. SRV - Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR653.3 ft. MGO - General Observation - MAG COAT 98% FINISH653.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG653.9 ft. AMH - Downstream Manhole, Survey Ends - 2:20AM

Observation photos (13)

  • General Observation - MAG COAT 98% 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 98% 9:00 TO 3:00

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    8 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Projecting, from 02 to 03 o'clock, within 8 inches of joint: NO - SEBVERE AGG UNDER MAG COAT

    41 ft. - Surface Aggregate Projecting, from 02 to 03 o'clock, within 8 inches of joint: NO - SEBVERE AGG UNDER MAG COAT

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGGUNDER MAG COAT

    89.5 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGGUNDER MAG COAT

  • Surface Aggregate Projecting, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

    99.6 ft. - Surface Aggregate Projecting, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Projecting, from 09 to 10 o'clock, within 8 inches of joint: YES - SEVERE AGG

    115.1 ft. - Surface Aggregate Projecting, from 09 to 10 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Aggregate Projecting, at 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

    131 ft. - Surface Aggregate Projecting, at 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    161.7 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    242.9 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

    518 ft. - Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    567.3 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

    647.4 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

  • Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    650 ft. - Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

Observations (19)

DistanceCodeObservation
131SAPSEVERE AGG
8SRVCIRCUM REBAR
653.3MGOMAG COAT 98% FINISH
115.1SAPSEVERE AGG
650SRVCIRCUM REBAR
653.9AMH2:20AM
99.6SAPSEVERE AGG
89.5SAPSEVERE AGGUNDER MAG COAT
647.4SRVLONG REBAR
41SAPSEBVERE AGG UNDER MAG COAT
0MWL
2MGOMAG COAT 98% 9:00 TO 3:00
567.3SRVCIRCUM REBAR
242.9SRVCIRCUM REBAR
0AMH1:20AM
653.3SAPSEVERE AGG
0MWM
161.7SRVCIRCUM REBAR
518SAPSEVERE AGG

Properties (4)

custom_field_three
CIRCUM& LONG REBAR
custom_field_two
2
customer
LACSD
datetime
2017-04-06T01:06:43-07:00