Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 21, 2017, 04:57 PM
  • A 0847_A 0846_2212017_092842.mp4

Date
02/21/2017
W/O
0613346
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00324
PipeID
P08187
Time
8:57 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7336
Sewer Name
A JOA-1A NORTH LONG BEACH INTERCEPTOR
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
20170221DF_JOA_1A_NORTH_LONG_BEACH_INTERCEPTOR
Material
Vitrified Clay Pipe
Shape
Circular
Height
33 in.
Upstream MH
A 0847
Downstream MH
A 0846
Dir. of Survey
Downstream
Length Surveyed
746.9 ft.
Total Length
746.9 ft.
Structural Index
3
Structural Quick
4138
Structural Rating
33
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
33
Pipe schematic from manhole A 0847 to A 0846
MH: A 0847MH: A 0846downstream0 ft. AMH - Upstream Manhole, Survey Begins - 9:02 AM0.1 ft. MWL - Water Level, 35 %of cross sectional area0.1 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. SSSC - Surface Spalling Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAVC - Surface Aggregate Visible Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start50.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES56.2 ft. CM - Crack Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES104.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLE MAG COAT PEELING493.7 ft. MMC - Material Change, Other (state in comments) - CONCRETE PIPE493.7 ft. MGP - General Photograph - POSSIBLE CONCRETE PIPE496.2 ft. MMC - Material Change, Vitrified clay pipe519.8 ft. MGO - General Observation - M537.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start543.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start543.5 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish566.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish568.1 ft. CC - Crack Circumferential, from 11 to 05 o'clock, within 8 inches of joint: YES572.3 ft. CM - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES591 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start620.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish632.1 ft. CM - Crack Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES735 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES, Start746.3 ft. SSSC - Surface Spalling Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish746.3 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES, Finish746.3 ft. SAVC - Surface Aggregate Visible Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish746.9 ft. AMH - Downstream Manhole, Survey Ends - 11:01 AM

Observation photos (16)

  • Surface Spalling Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    50.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES

    56.2 ft. - Crack Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLE MAG COAT PEELING

    104.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLE MAG COAT PEELING

  • Material Change, Other (state in comments) - CONCRETE PIPE

    493.7 ft. - Material Change, Other (state in comments) - CONCRETE PIPE

  • General Photograph - POSSIBLE CONCRETE PIPE

    493.7 ft. - General Photograph - POSSIBLE CONCRETE PIPE

  • Material Change, Vitrified clay pipe

    496.2 ft. - Material Change, Vitrified clay pipe

  • General Observation - M

    519.8 ft. - General Observation - M

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start

    537.4 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    543.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Circumferential, from 11 to 05 o'clock, within 8 inches of joint: YES

    568.1 ft. - Crack Circumferential, from 11 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    572.3 ft. - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    591 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

    632.1 ft. - Crack Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES, Start

    735 ft. - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
50.2FL
746.3SSSC
2SSSC
493.7MMCCONCRETE PIPE
537.4FL
746.3CM
620.4CM
735CM
632.1CM
496.2MMC
572.3CM
56.2CM
2SAVC
0.1MWL
0.1MWM
566.7FM
746.9AMH11:01 AM
543.5FM
591CM
104.1CLPOSSIBLE MAG COAT PEELING
568.1CC
519.8MGOM
0AMH9:02 AM
493.7MGPPOSSIBLE CONCRETE PIPE
543.5FL
746.3SAVC

Properties (3)

custom_field_two
2
customer
LACSD
datetime
2017-02-21T08:57:05-08:00