08 0003_08 0002_2222017_033321.mp4
2 ft. - General Observation - MISSING TILES 90% START
2.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR
10.9 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
10.9 ft. - General Observation - MISSING TILES 100% START
20.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR
26.1 ft. - General Observation - 50% TILES
55.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES
74.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR
109 ft. - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR
168.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES
| Distance | Code | Observation |
|---|---|---|
| 273.2 | MGO | Conn. @ Mh, 9 O' Clock. Active |
| 219.7 | MGO | 1 ROW TILE |
| 20.7 | SRC | LONG CIRCUM REBAR |
| 248.5 | MGO | 3 ROW TILES |
| 273.6 | AMH | 3:45AM |
| 273.2 | MGO | Conn. @ Mh, 3 O' Clock. Active |
| 26.1 | MGO | 50% TILES |
| 273.2 | MGO | MISSING TILES 100% FINISH |
| 2 | MGO | MISSING TILES 90% START |
| 10.9 | SRC | CIRCUM REBAR |
| 74.7 | SRC | LONG CIRCUM REBAR |
| 211.2 | MGO | 1 ROW TILE |
| 273.2 | SAM | SEVERE AGG |
| 264.7 | MGO | 2 ROW TILES |
| 109 | SRC | BROKEN REBAR |
| 55.6 | SRC | — |
| 273.2 | SRC | LONG CIRCUM REBAR |
| 2.5 | SRC | LONG CIRCUM REBAR |
| 0 | AMH | 3:10AM |
| 168.2 | SRC | — |
| 0 | MWM | — |
| 0 | MWL | — |
| 2 | SAM | SEVERE AGG |
| 97.3 | MGO | 3 ROWS TIILES |
| 4.6 | MGO | 2 ROWS TILES |
| 10.9 | MGO | MISSING TILES 100% START |
| 0 | MGO | Conn. @ Mh, 9 O' Clock. OPEN 100% GREASE BLOCKED |