Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 22, 2017, 09:11 AM
  • 08 0005_08 0004_2222017_015700.mp4

Date
02/22/2017
W/O
0613373
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00016
PipeID
P00005
Time
1:11 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0452
Sewer Name
08 MAIN STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20170217MDM_MAIN_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
08 0005
Downstream MH
08 0004
Dir. of Survey
Downstream
Length Surveyed
275.4 ft.
Total Length
275.4 ft.
Structural Index
5
Structural Quick
5641
Structural Rating
34
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
38
Pipe schematic from manhole 08 0005 to 08 0004
MH: 08 0005MH: 08 0004downstream0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:20AM0 ft. MWL - Water Level, 40 %of cross sectional area8 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start AREAS OF MISSING TILES - SEVERE AGG8 ft. MGO - General Observation - MISSING TILES 100% START11.4 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR13.9 ft. SRC - Surface Reinforcement Corroded, from 11 to 03 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR18.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR18.4 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR19.9 ft. MGP - General Photograph - CORRODED REBAR42.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES52.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES73.6 ft. MGO - General Observation - 1 ROW TILES127.4 ft. MGO - General Observation - 1 ROW TILES214.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO244.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8" - Active275 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AQG275 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR275.4 ft. AMH - Downstream Manhole, Survey Ends - 2:00AM

Observation photos (9)

  • General Observation - MISSING TILES 100% START

    8 ft. - General Observation - MISSING TILES 100% START

  • Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    11.4 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 03 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

    13.9 ft. - Surface Reinforcement Corroded, from 11 to 03 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    18.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • General Photograph - CORRODED REBAR

    19.9 ft. - General Photograph - CORRODED REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

    42.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

    52.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - 1 ROW TILES

    73.6 ft. - General Observation - 1 ROW TILES

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO

    214.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO

Observations (19)

DistanceCodeObservation
8SAMSEVERE AGG
275SAMSEVERE AQG
214.4SRC
19.9MGPCORRODED REBAR
18.4SRCLONG CIRCUM REBAR
275.4AMH2:00AM
13.9SRCLONG CIRCUM REBAR
275SRCLONG CIRCUM REBAR
8MGOMISSING TILES 100% START
52.7SRC
18.4SRCCIRCUM REBAR
244.9TFActive
0MWM
73.6MGO1 ROW TILES
0AMH1:20AM
42.1SRC
127.4MGO1 ROW TILES
11.4SRCCIRCUM REBAR
0MWL

Properties (4)

custom_field_three
CORRODED LONG CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2017-02-22T01:11:34-08:00