Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 21, 2017, 08:54 AM
  • 08 0008_08 0007_2212017_015739.mp4

Date
02/21/2017
W/O
0613622
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00016
PipeID
P00008
Time
12:54 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0451
Sewer Name
08 MAIN STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20170217MDM_MAIN_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
08 0008
Downstream MH
08 0007
Dir. of Survey
Downstream
Length Surveyed
300.5 ft.
Total Length
300.5 ft.
Structural Index
5
Structural Quick
5B41
Structural Rating
79
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
84
Pipe schematic from manhole 08 0008 to 08 0007
MH: 08 0008MH: 08 0007downstream0 ft. MWL - Water Level, 60 %of cross sectional area0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:25AM13.1 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES13.1 ft. MGO - General Observation - MISSING TILES 100% 10:00 TO 2:00 START13.4 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR23.5 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR27.7 ft. MGO - General Observation - MISSING TILES 10% START38.4 ft. MGO - General Observation - MISSING TILES 40%43.9 ft. MGO - General Observation - MISSING TILES 30%% START58 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR60 ft. MGO - General Observation - MISSING TILES 10% START68.7 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR68.7 ft. MGO - General Observation - MISSING TILES 100%108.7 ft. MGO - General Observation - MISSING TILES 100%109.9 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR127.8 ft. MGO - General Observation - MISSING TLES 60%131.6 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR134.1 ft. MGO - General Observation - MISSING TILES 10%143.3 ft. MGO - General Observation - MISSING TILES 40%151.9 ft. MGO - General Observation - MISSING TILES 100% START153.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR155.3 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR156.7 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR161.2 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR172 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish172 ft. MGO - General Observation - MISSING TLES 10%180.6 ft. MGO - General Observation - MISSING TILES 100%184.5 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR189.4 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR194.9 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR195.7 ft. MGO - General Observation - MISSING TILES 100%201.3 ft. SRC - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR224.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR270.2 ft. SRC - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR271.9 ft. MGO - General Observation - MISSING TILES 30%300.1 ft. SRC - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR300.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped300.1 ft. MGO - General Observation - MISSING TILES 100% FINISH300.1 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG AREAS OF MISSING TILES300.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active300.5 ft. AMH - Downstream Manhole, Survey Ends - 2:25AM

Observation photos (23)

  • General Observation - MISSING TILES 100% 10:00 TO 2:00 START

    13.1 ft. - General Observation - MISSING TILES 100% 10:00 TO 2:00 START

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    13.4 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    23.5 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    58 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    68.7 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • General Observation - MISSING TILES 100%

    108.7 ft. - General Observation - MISSING TILES 100%

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    109.9 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - MISSING TLES 60%

    127.8 ft. - General Observation - MISSING TLES 60%

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    131.6 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • General Observation - MISSING TILES 10%

    134.1 ft. - General Observation - MISSING TILES 10%

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG  CIRCUM REBAR

    153.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

    155.3 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    156.7 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

    161.2 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

  • General Observation - MISSING TLES 10%

    172 ft. - General Observation - MISSING TLES 10%

  • General Observation - MISSING TILES 100%

    180.6 ft. - General Observation - MISSING TILES 100%

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    184.5 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR

    194.9 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR

  • General Observation - MISSING TILES 100%

    195.7 ft. - General Observation - MISSING TILES 100%

  • Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    201.3 ft. - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    224.7 ft. - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

    270.2 ft. - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

  • General Observation - MISSING TILES 30%

    271.9 ft. - General Observation - MISSING TILES 30%

Observations (42)

DistanceCodeObservation
13.1SAMSEVERE AGG AREAS OF MISSING TILES
172SRC
195.7MGOMISSING TILES 100%
108.7MGOMISSING TILES 100%
172MGOMISSING TLES 10%
0MWL
109.9SRCCIRCUM REBAR
23.5SRCLONG CIRCUM REBAR
300.1SRCLONG CIRCUM REBAR
189.4SRCLONG CIRCUM REBAR
151.9MGOMISSING TILES 100% START
143.3MGOMISSING TILES 40%
300.1MGOConn. @ Mh, 9 O' Clock. Capped
27.7MGOMISSING TILES 10% START
38.4MGOMISSING TILES 40%
155.3SRCLONG REBAR
224.7SRCCIRCUM REBAR
194.9SRCLONG REBAR
300.1MGOMISSING TILES 100% FINISH
271.9MGOMISSING TILES 30%
300.5AMH2:25AM
180.6MGOMISSING TILES 100%
300.1SAMSEVERE AGG AREAS OF MISSING TILES
127.8MGOMISSING TLES 60%
161.2SRCLONG CIRCUM REBAR
0MWM
60MGOMISSING TILES 10% START
300.1MGOConn. @ Mh, 3 O' Clock. Active
58SRCLONG CIRCUM REBAR
131.6SRVCIRCUM REBAR
43.9MGOMISSING TILES 30%% START
13.1MGOMISSING TILES 100% 10:00 TO 2:00 START
156.7SRCCIRCUM REBAR
201.3SRCLONG CIRCUM REBAR
68.7SRVCIRCUM REBAR
153.7SRCLONG CIRCUM REBAR
0AMH1:25AM
134.1MGOMISSING TILES 10%
68.7MGOMISSING TILES 100%
270.2SRCLONG CIRCUM REBAR
13.4SRVCIRCUM REBAR
184.5SRCLONG CIRCUM REBAR

Properties (4)

custom_field_three
CORRODED LONG CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2017-02-21T00:54:56-08:00