Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 16, 2017, 12:29 PM
  • 08 0036_08 0035_2162017_043958.mp4

Date
02/16/2017
W/O
0613622
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00016
PipeID
P00038
Time
4:29 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0445
Sewer Name
08 MAIN STREET TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20170215MDM_MAIN_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
08 0036
Downstream MH
08 0035
Dir. of Survey
Downstream
Length Surveyed
323.7 ft.
Total Length
323.7 ft.
Structural Index
3
Structural Quick
4138
Structural Rating
50
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
52
Pipe schematic from manhole 08 0036 to 08 0035
MH: 08 0036MH: 08 0035downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:35AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area32.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped54.9 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - HAIRLINE58.8 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE58.8 ft. SSS - Surface Spalling, from 07 to 09 o'clock, within 8 inches of joint: YES59.9 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - SLIGHT59.9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE62 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - H64.6 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE72.4 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES83.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped132.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped186.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped186.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE190.9 ft. FS - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES - SLIGHT190.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H191.4 ft. FS - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT191.4 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SLIGHT191.4 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H192.4 ft. SSS - Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO194.4 ft. FM - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT196.5 ft. FS - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES, Finish196.9 ft. FS - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT196.9 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES197.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H199.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT201.3 ft. FS - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish203.2 ft. FM - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES, Finish - SLIGHHT206.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT234.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped269.9 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H276.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H276.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped293.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H323.7 ft. AMH - Downstream Manhole, Survey Ends - 5:40AM

Observation photos (10)

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    54.9 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE

    58.8 ft. - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE

  • Surface Spalling, from 07 to 09 o'clock, within 8 inches of joint: YES

    58.8 ft. - Surface Spalling, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    186.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    191.4 ft. - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO

    192.4 ft. - Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO

  • Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    194.4 ft. - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    196.9 ft. - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

    196.9 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    197.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

Observations (37)

DistanceCodeObservation
83.9TFCCapped
0AMH4:35AM
72.4DSGV
32.4TFCCapped
206.3FLSLIGHT
0MWM
196.5FS
62FCH
54.9FLHAIRLINE
196.9FSSLIGHT
199.4FCSLIGHT
132.6TFCCapped
190.9FSSLIGHT
64.6FLHAIRLINE
190.9FLH
323.7AMH5:40AM
293.7FCH
186.7FLHAIRLINE
58.8FCHAIRLINE
276.3FLH
58.8SSS
186.3TFCCapped
192.4SSS
201.3FS
0MWL
191.4FSSLIGHT
269.9FCH
276.4TFCCapped
59.9FLSLIGHT
191.4FCSLIGHT
196.9SSS
194.4FMSLIGHT
59.9FCHAIRLINE
203.2FMSLIGHHT
197.3FLH
234.6TFCCapped
191.4FCH

Properties (4)

custom_field_three
MULTIPLE SLIGHT FRACTURES JOINT TO JOINT
custom_field_two
2
customer
LACSD
datetime
2017-02-16T04:29:57-08:00