Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2017, 10:37 AM
  • 05 1772_05 1771A_272017_025355.mp4

Date
02/07/2017
W/O
0607790
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00473
PipeID
P07000
Time
2:37 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0433
Sewer Name
05 LOMITA TRUNK EXTENSION
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Capital Improvement Program Assesment
Project
20170207MDM_LOMITA_TRUNK_EXTENSION
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 1771A
Downstream MH
05 1772
Dir. of Survey
Upstream
Length Surveyed
547.6 ft.
Total Length
547.6 ft.
Structural Index
2
Structural Quick
4135
Structural Rating
138
O&M Index
2
O&M Quick
4236
O&M Rating
33
Overall Index
2
Overall Quick
Overall Rating
171
Pipe schematic from manhole 05 1771A to 05 1772
MH: 05 1771AMH: 05 1772upstream0 ft. AMH - Upstream Manhole, Survey Ends - 4:30AM0.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped0.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped0.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H10.1 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H26.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H34.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H38.2 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL62.2 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL66.9 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL74.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL78.3 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SL78.8 ft. JOM - Joint Offset Medium86.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT94.3 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SL98.6 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - H98.6 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H106.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL110.6 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H113.6 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 10 %, within 8 inches of joint: YESR, Finish - 10% OR LESS115.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL123.2 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - SL126.9 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - H135.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE138.8 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - SL151.3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL154.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL162.9 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL162.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL167.5 ft. MWM - Water Mark, 60 %of cross sectional area171.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL207.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H211.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H212 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL212 ft. FC - Fracture Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES - SL215.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SL224 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL235.7 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL235.7 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL239.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - MODERATE239.9 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - MODERATE247.3 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR257.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active284.3 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H300 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H304.8 ft. FC - Fracture Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES - SL308.6 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - SL308.6 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H316.6 ft. MWM - Water Mark, 50 %of cross sectional area316.6 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - SL316.6 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL320.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL320.6 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL325.3 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 10 %, within 8 inches of joint: YESR, Start - 10% OR LESS328.5 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR328.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT335.1 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 25 %, within 8 inches of joint: YESR336.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL336.7 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - MODERATE336.7 ft. FC - Fracture Circumferential, from 08 to 03 o'clock, within 8 inches of joint: YES - SL336.7 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR338.3 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 10 %, within 8 inches of joint: YESR, Finish340.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL340.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL340.4 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL352.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL356.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL359.2 ft. RFJ - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YESR, Finish - 5% OR LESS359.2 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 10 %, within 8 inches of joint: YESR, Start389.1 ft. RFJ - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YESR, Start - 5% OR LISS401 ft. RFJ - Roots Fine Joint, from 03 to 05 o'clock, within 8 inches of joint: YESR - 2%404.8 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SL405.2 ft. RFJ - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YESR - 4%409.3 ft. RFJ - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YESR - 5%409.3 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL412.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT421 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL425 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL441.7 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H445.6 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - SL449.8 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - SL453.9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT453.9 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H465.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL465.5 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - SLIGHT490 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YESR - 2%498.2 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YESR - 1%505.9 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YESR - 3%513.7 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H530.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE538.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL547.6 ft. AMH - Downstream Manhole, Survey Begins - 2:45AM-ABANDONED MH-CAPPED547.6 ft. MWL - Water Level, 10 %of cross sectional area547.6 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (16)

  • Downstream Manhole, Survey Begins - 2:45AM-ABANDONED MH-CAPPED

    0 ft. - Downstream Manhole, Survey Begins - 2:45AM-ABANDONED MH-CAPPED

  • Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YESR, Start - 5% OR LISS

    158.5 ft. - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YESR, Start - 5% OR LISS

  • Roots Medium Joint, from 03 to 09 o'clock, 10 %, within 8 inches of joint: YESR, Start

    188.4 ft. - Roots Medium Joint, from 03 to 09 o'clock, 10 %, within 8 inches of joint: YESR, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    191.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - MODERATE

    210.9 ft. - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - MODERATE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    211.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Roots Medium Joint, from 03 to 09 o'clock, 25 %, within 8 inches of joint: YESR

    212.5 ft. - Roots Medium Joint, from 03 to 09 o'clock, 25 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR

    219.1 ft. - Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 03 to 09 o'clock, 10 %, within 8 inches of joint: YESR, Start - 10% OR LESS

    222.3 ft. - Roots Medium Joint, from 03 to 09 o'clock, 10 %, within 8 inches of joint: YESR, Start - 10% OR LESS

  • Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR

    300.3 ft. - Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR

  • Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - MODERATE

    307.7 ft. - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - MODERATE

  • Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - MODERATE

    307.7 ft. - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - MODERATE

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SL

    331.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SL

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    336.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE

    412.5 ft. - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE

  • Joint Offset Medium

    468.8 ft. - Joint Offset Medium

Observations (94)

DistanceCodeObservation
307.7FCMODERATE
311.9FCSL
485.4FCSL
460.9FCSLIGHT
219.1RMJ
537.5FCH
521.1FCH
336.4FLH
231MWM
138.3RFJ5%
210.9FCMODERATE
122.6FCSL
0AMH2:45AM-ABANDONED MH-CAPPED
384.7FCSL
392.7FCSL
231FCSL
290.4TBActive
307.7FCMODERATE
222.3RMJ10% OR LESS
437FCH
547.6AMH4:30AM
212.5RMJ
340.3FLH
207.2FCSL
211.2FLSL
424.4FCSL
138.3FCSL
102FCSL
57.6RFJ2%
441FCSL
17.5FCHAIRLINE
41.7RFJ3%
93.7FCSLIGHT
469.3FCSL
335.6FCSL
158.5RFJ5% OR LISS
188.4RFJ5% OR LESS
82.1FCSL
547.3MGOConn. @ Mh, 9 O' Clock. Capped
547.3MGOConn. @ Mh, 3 O' Clock. Capped
209.3RMJ
546.9FCH
82.1FCSLIGHT
509.4FCSL
449FCH
396.3FCSL
239FCSL
453.3FCSL
468.8JOM
242.8FCSL
105.9FCH
142.8FCSL
134.8FCSLIGHT
331.9FMSL
210.9FCSL
188.4RMJ
227FCSL
207.2FLSL
335.6FCSL
227FCSL
126.6FCSL
239FCH
247.6FCH
434RMJ10% OR LESS
146.6RFJ2%
49.4RFJ1%
33.9FCH
263.3FCH
408.8FLSL
412.5FCMODERATE
0MWL
420.7FCH
376.3FCSL
311.9FCSL
0MWM
480.7FCSL
432.4FCSL
194.9FCSL
9.2FCSL
142.4RFJ4%
97.8FCSL
207.2FCSL
449FLH
93.7FCH
231FCSL
384.7FCSL
380.1MWM
191.3FLSL
300.3RMJ
323.6FCSL
210.9RMJ
472.9FCSL
513FCH
219.1FLSLIGHT

Properties (4)

custom_field_three
SLIGHT LONG FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2017-02-07T02:37:34-08:00