Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 9, 2017, 08:45 AM
  • 08 0465_08 0464_292017_012816.mp4

Date
02/09/2017
W/O
0622893
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00521
Time
12:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
H0437
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20170203MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0465
Downstream MH
08 0464
Dir. of Survey
Downstream
Length Surveyed
498.6 ft.
Total Length
498.6 ft.
Structural Index
5
Structural Quick
5300
Structural Rating
15
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
20
Pipe schematic from manhole 08 0465 to 08 0464
MH: 08 0465MH: 08 0464downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:25AM0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 75 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING REBAR10.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open275.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active275.2 ft. SMW - Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: YES - SOIL276.6 ft. SMW - Surface Missing Wall, at 02 o'clock, within 8 inches of joint: YES - 6" X6"303.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active316.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open357.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active498.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CORRODED MISSING REBAR498.3 ft. MGO - General Observation - Conn. @ Mh, 12 O' Clock. Capped498.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active498.6 ft. AMH - Downstream Manhole, Survey Ends - 2:30AM

Observation photos (2)

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING REBAR

  • Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: YES - SOIL

    275.2 ft. - Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: YES - SOIL

Observations (16)

DistanceCodeObservation
10.3TFOpen
498.3SRCCORRODED MISSING REBAR
0AMH1:25AM
316.9TFOpen
2SRCCORRODED MISSING REBAR
498.6AMH2:30AM
357.2TFActive
498.3MGOConn. @ Mh, 12 O' Clock. Capped
275.2TFActive
0MWM
276.6SMW6" X6"
0MGOConn. @ Mh, 3 O' Clock. Active
0MWL
275.2SMWSOIL
303.1TFActive
498.3MGOConn. @ Mh, 9 O' Clock. Active

Properties (4)

custom_field_three
MISSING WALL SOIL VISIBLE
custom_field_two
1
customer
LACSD
datetime
2017-02-09T00:45:14-08:00