Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2017, 09:28 AM
  • F 0152_F 0151_222017_013944.mp4

Date
02/02/2017
W/O
0621268
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00038
PipeID
P10184
Time
1:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0425
Sewer Name
F JOINT OUTFALL F - UNIT 3C
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Capital Improvement Program Assesment
Project
20170201MDM_JOINT_OUTFALL_F_UNIT_3C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Upstream MH
F 0152
Downstream MH
F 0151
Dir. of Survey
Downstream
Length Surveyed
713.8 ft.
Total Length
713.8 ft.
Structural Index
4
Structural Quick
5343
Structural Rating
29
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
29
Pipe schematic from manhole F 0152 to F 0151
MH: F 0152MH: F 0151downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:30AM2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG2 ft. MGO - General Observation - MAG COAT 90% 8:00 TO 4:00 START37.8 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR41.1 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES - FLACKING CONCRETE96.8 ft. SAM - Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG228.2 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR238 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM & LONG REBAR265.4 ft. SAM - Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG588.2 ft. MGO - General Observation - 90% MAGCOAT713.5 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG UNDER MAG COAT713.5 ft. MGO - General Observation - MAG COAT 90% FINISH713.8 ft. AMH - Downstream Manhole, Survey Ends - 2:35AM

Observation photos (8)

  • General Observation - MAG COAT 90% 8:00 TO 4:00 START

    2 ft. - General Observation - MAG COAT 90% 8:00 TO 4:00 START

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    37.8 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES - FLACKING CONCRETE

    41.1 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES - FLACKING CONCRETE

  • Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    96.8 ft. - Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    228.2 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM & LONG REBAR

    238 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM & LONG REBAR

  • Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    265.4 ft. - Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - 90% MAGCOAT

    588.2 ft. - General Observation - 90% MAGCOAT

Observations (15)

DistanceCodeObservation
713.8AMH2:35AM
37.8SRVCIRCUM REBAR
0MWL
0MWM
713.5SAMSEVERE AGG UNDER MAG COAT
2SAMSEVERE AGG UNDER MAG
238SRVCIRCUM & LONG REBAR
2MGOMAG COAT 90% 8:00 TO 4:00 START
265.4SAMSEVERE AGG
96.8SAMSEVERE AGG
228.2SRVCIRCUM REBAR
41.1SSSFLACKING CONCRETE
588.2MGO90% MAGCOAT
713.5MGOMAG COAT 90% FINISH
0AMH1:30AM

Properties (4)

custom_field_three
VISIBLE CIRCUM & LONG REBAR-90% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2017-02-02T01:28:36-08:00