Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 27, 2017, 08:30 AM
  • 03 0327_03 0326_1272017_012117.mp4

Date
01/27/2017
W/O
0619904
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00359
PipeID
P04901
Time
12:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0416
Sewer Name
03 ANAHEIM STREET TRUNK
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Capital Improvement Program Assesment
Project
20170125MDM_ANAHEIM_STREET_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
03 0327
Downstream MH
03 0326
Dir. of Survey
Downstream
Length Surveyed
186.8 ft.
Total Length
186.8 ft.
Structural Index
3
Structural Quick
4221
Structural Rating
10
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole 03 0327 to 03 0326
MH: 03 0327MH: 03 0326downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:15AM10 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG100 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG172.6 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - PEELING CONCRETE THROUGHOUT REACH186.4 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG186.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN186.8 ft. AMH - Downstream Manhole, Survey Ends - 1:35AM

Observation photos (3)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    10 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE  AGG

    100 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - PEELING CONCRETE THROUGHOUT REACH

    172.6 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - PEELING CONCRETE THROUGHOUT REACH

Observations (10)

DistanceCodeObservation
186.8AMH1:35AM
172.6SSSPEELING CONCRETE THROUGHOUT REACH
10SAMSEVERE AGG
100SAMSEVERE AGG
186.4SAMSEVERE AGG
186.4MGOConn. @ Mh, 3 O' Clock. OPEN
0MGOConn. @ Mh, 3 O' Clock. OPEN
0MWL
0MWM
0AMH1:15AM

Properties (4)

custom_field_three
PEELING CONCRETE MISSING SEVERE AGG
custom_field_two
1
customer
LACSD
datetime
2017-01-27T00:30:28-08:00