Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 24, 2017, 08:58 AM
  • B 1500_B 1499_1242017_042935.mp4

Date
01/24/2017
W/O
061723
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01124
PipeID
P25615
Time
12:58 AM
Certificate
U-1014-0602253
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0409
Sewer Name
B JOINT OUTFALL B - UNIT 6G
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
23
Purpose
Capital Improvement Program Assesment
Project
20170124MDM_JOINT_OUTFALL_B_UNIT_6G
Material
Vitrified Clay Pipe
Shape
Circular
Height
36 in.
Upstream MH
B 1500
Downstream MH
B 1499
Dir. of Survey
Downstream
Length Surveyed
606.7 ft.
Total Length
606.7 ft.
Structural Index
5
Structural Quick
5831
Structural Rating
43
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
43
Pipe schematic from manhole B 1500 to B 1499
MH: B 1500MH: B 1499downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:25AM0 ft. MWL - Water Level, 20 %of cross sectional area57.2 ft. SMW - Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE115.9 ft. SMW - Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: YES - VOD SOIL VISIBLE115.9 ft. SMW - Surface Missing Wall, at 11 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE130.3 ft. SMW - Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - VOID SOIL VISIBLE131.7 ft. SMW - Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE137.8 ft. SMW - Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - VOID SOIL VISIBLE205.9 ft. SMW - Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE211.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT214.6 ft. SMW - Surface Missing Wall, from 12 to 02 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE282.1 ft. SMW - Surface Missing Wall, from 01 to 03 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE596.3 ft. MGO - General Observation - 36" VCP606.7 ft. AMH - Downstream Manhole, Survey Ends - 5:15AM

Observation photos (10)

  • Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

    57.2 ft. - Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

  • Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: YES - VOD SOIL VISIBLE

    115.9 ft. - Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: YES - VOD SOIL VISIBLE

  • Surface Missing Wall, at 11 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

    115.9 ft. - Surface Missing Wall, at 11 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

  • Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - VOID SOIL VISIBLE

    130.3 ft. - Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - VOID SOIL VISIBLE

  • Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

    131.7 ft. - Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

  • Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - VOID SOIL VISIBLE

    137.8 ft. - Surface Missing Wall, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - VOID SOIL VISIBLE

  • Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

    205.9 ft. - Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

  • Surface Missing Wall, from 12 to 02 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

    214.6 ft. - Surface Missing Wall, from 12 to 02 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

  • Surface Missing Wall, from 01 to 03 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

    282.1 ft. - Surface Missing Wall, from 01 to 03 o'clock, within 8 inches of joint: YES - VOID SOIL VISIBLE

  • General Observation - 36" VCP

    596.3 ft. - General Observation - 36" VCP

Observations (15)

DistanceCodeObservation
115.9SMWVOD SOIL VISIBLE
0MWM
115.9SMWVOID SOIL VISIBLE
57.2SMWVOID SOIL VISIBLE
131.7SMWVOID SOIL VISIBLE
214.6SMWVOID SOIL VISIBLE
0AMH4:25AM
0MWL
596.3MGO36" VCP
211.2FLSLIGHT
205.9SMWVOID SOIL VISIBLE
282.1SMWVOID SOIL VISIBLE
130.3SMWVOID SOIL VISIBLE
137.8SMWVOID SOIL VISIBLE
606.7AMH5:15AM

Properties (4)

custom_field_three
VOIDS SOIL VISIBLE
custom_field_two
1
customer
LACSD
datetime
2017-01-24T00:58:50-08:00