Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 23, 2017, 06:43 PM
  • 01 0353_01 0352_1232017_104558.mp4

Date
01/23/2017
W/O
0613369
Weather
Heavy Rain
Operator/Surveyor
FRANKLIN
Sewer ID
Z00215
PipeID
P00827
Time
10:43 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7315
Sewer Name
01 NADEAU TRUNK, SECTS 2&1
City
SOUTH L.A.
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
03
Purpose
Capital Improvement Program Assesment
Project
20170120DF_NADEAU_TRUNK_SECTS_1_AND_2
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 0353
Downstream MH
01 0352
Dir. of Survey
Downstream
Length Surveyed
435.8 ft.
Total Length
435.8 ft.
Structural Index
4
Structural Quick
5643
Structural Rating
55
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
55
Pipe schematic from manhole 01 0353 to 01 0352
MH: 01 0353MH: 01 0352downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 10:44 AM2 ft. SAVC - Surface Aggregate Visible Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSSC - Surface Spalling Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.6 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES44.3 ft. B - Broken, from 07 to 10 o'clock, within 8 inches of joint: YES79.7 ft. B - Broken, from 07 to 05 o'clock, within 8 inches of joint: YES79.7 ft. B - Broken, from 02 to 04 o'clock, within 8 inches of joint: YES120.3 ft. B - Broken, from 07 to 09 o'clock, within 8 inches of joint: YES135.4 ft. B - Broken, from 07 to 09 o'clock, within 8 inches of joint: YES160.9 ft. B - Broken, from 03 to 04 o'clock, within 8 inches of joint: YES216.7 ft. B - Broken, from 08 to 03 o'clock, within 8 inches of joint: YES216.7 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES237.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES293 ft. B - Broken, from 08 to 09 o'clock, within 8 inches of joint: YES435.7 ft. MGO - General Observation - ROACHES @ MH435.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish435.7 ft. SAVC - Surface Aggregate Visible Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish435.7 ft. SSSC - Surface Spalling Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish435.8 ft. AMH - Downstream Manhole, Survey Ends - 11:19 AM

Observation photos (11)

  • Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    23.6 ft. - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Broken, from 07 to 10 o'clock, within 8 inches of joint: YES

    44.3 ft. - Broken, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Broken, from 07 to 05 o'clock, within 8 inches of joint: YES

    79.7 ft. - Broken, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Broken, from 02 to 04 o'clock, within 8 inches of joint: YES

    79.7 ft. - Broken, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 07 to 09 o'clock, within 8 inches of joint: YES

    120.3 ft. - Broken, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Broken, from 07 to 09 o'clock, within 8 inches of joint: YES

    135.4 ft. - Broken, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Broken, from 03 to 04 o'clock, within 8 inches of joint: YES

    160.9 ft. - Broken, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 03 o'clock, within 8 inches of joint: YES

    216.7 ft. - Broken, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    216.7 ft. - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    237.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 09 o'clock, within 8 inches of joint: YES

    293 ft. - Broken, from 08 to 09 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
293B
44.3B
0MWM
23.6FC
435.7MGOROACHES @ MH
120.3B
237.2CM
2SAVC
435.7CM
216.7B
435.7SAVC
435.7SSSC
160.9B
135.4B
0MWL
0AMH10:44 AM
435.8AMH11:19 AM
79.7B
2SSSC
79.7B
216.7FM
2CM

Properties (3)

custom_field_two
1
customer
LACSD
datetime
2017-01-23T10:43:15-08:00