Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 18, 2017, 09:22 PM
  • 02 1652_02 1651_1182017_132449.mp4

Date
01/18/2017
W/O
0613356
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00289
PipeID
P18807
Time
1:22 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7313
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
EAST L.A.
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
20170118DF_MONTEREY_PARK_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1652
Downstream MH
02 1651
Dir. of Survey
Downstream
Length Surveyed
310.4 ft.
Total Length
310.4 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 1652 to 02 1651
MH: 02 1652MH: 02 1651downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:23 PM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSSC - Surface Spalling Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start75.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"111.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"122.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"163 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"182.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"185.7 ft. TBD - Tap Break-In Defective, at 01 o'clock, -, , within 8 inches of joint: YES, 4" - OPEN213.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"220.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"245.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"264.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"309.5 ft. SSSC - Surface Spalling Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish310.3 ft. MGO - General Observation - STOP LOG DOWN @ 12 O'CLOCK310.3 ft. MGO - General Observation - STOP LOG @ 3 O'CLOCK310.4 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH310.4 ft. MGO - General Observation - ROACHES @ MH310.4 ft. AMH - Downstream Manhole, Survey Ends - 1:46 PM

Observations (22)

DistanceCodeObservation
75.2TFC
309.5SSSC
185.7TBDOPEN
2SSSC
0MWL
122.7TFC
0AMH1:23 PM
310.4MGOGREASE THROUGHOUT THE REACH
310.4MGOROACHES @ MH
0MGOConn. @ Mh, 3 O' Clock. Active
163TFC
220.5TBA
310.3MGOSTOP LOG DOWN @ 12 O'CLOCK
245.8TF
0MGOROACHES @ MH
0MWM
213.9TFC
264.6TFA
310.3MGOSTOP LOG @ 3 O'CLOCK
310.4AMH1:46 PM
182.1TFC
111.1TFC

Properties (3)

custom_field_two
4
customer
LACSD
datetime