Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2017, 03:56 PM
  • 29 0079_29 0078_1102017_081456.mp4

Date
01/10/2017
W/O
0607761
Weather
Light Rain
Operator/Surveyor
FRANKLIN
Sewer ID
Z00265
PipeID
P23859
Time
7:56 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7301
Sewer Name
29 33RD STREET TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
20170110DF_33RD_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0079
Downstream MH
29 0078
Dir. of Survey
Downstream
Length Surveyed
142.3 ft.
Total Length
142.3 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
41
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
41
Pipe schematic from manhole 29 0079 to 29 0078
MH: 29 0079MH: 29 0078downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:00 AM0.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0.1 ft. MGO - General Observation - ROACHES @ MH0.1 ft. MWL - Water Level, 15 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAVC - Surface Aggregate Visible Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSSC - Surface Spalling Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES9.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES18.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES30.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES33.9 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES36.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES42.8 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES52.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - OPEN55.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - OPEN62.6 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES74.8 ft. B - Broken, from 07 to 09 o'clock, within 8 inches of joint: YES81 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES83.3 ft. JOM - Joint Offset Medium, 1"102 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES117 ft. CS - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES141.3 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH141.3 ft. SAVC - Surface Aggregate Visible Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish141.3 ft. SSSC - Surface Spalling Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish141.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish142.3 ft. AMH - Downstream Manhole, Survey Ends - 8:39 AM

Observation photos (12)

  • Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    2.5 ft. - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    9.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    18.5 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    30.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    33.9 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    36.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    42.8 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    62.6 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Broken, from 07 to 09 o'clock, within 8 inches of joint: YES

    74.8 ft. - Broken, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    81 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    102 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

    117 ft. - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
0MWM
42.8CL
0AMH8:00 AM
62.6CL
142.3AMH8:39 AM
0.1MGOConn. @ Mh, 3 O' Clock. Active
141.3MGOSLIGHT GREASE THROUGHOUT THE REACH
117CS
9.3FL
2CM
83.3JOM
102FM
0.1MGOROACHES @ MH
81FL
33.9CL
141.3SAVC
36.7CL
55.1TFOPEN
74.8B
30.7CL
0.1MWL
141.3SSSC
2SAVC
52.6TFOPEN
2.5CM
141.3CM
2SSSC
18.5CL