Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2017, 11:28 AM
  • 05 0678_05 0677_1122017_033211.mp4

Date
01/12/2017
W/O
0607750
Weather
Heavy Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00523
PipeID
P05910
Time
3:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0387
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #2
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
11
Purpose
Routine Assessment
Project
20170109MDM_SOUTH_INGLEWOOD_ORANGE_AVENUE_TRUNK_EXTENSION_2
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
05 0678
Downstream MH
05 0677
Dir. of Survey
Downstream
Length Surveyed
342.4 ft.
Total Length
342.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2500
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 05 0678 to 05 0677
MH: 05 0678MH: 05 0677downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:35AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area10.2 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-40% ROOTS13.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS41.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-80% ROOTS66.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped79.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open85.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-40% ROOTS122.9 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active-50% ROOTS156.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open159.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped180.9 ft. MGO - General Observation - 12" VCP209.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open212.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open246.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open250.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open290.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open293.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active303.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open324.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active342.4 ft. AMH - Downstream Manhole, Survey Ends - 4:05AM

Observation photos (1)

  • General Observation - 12" VCP

    180.9 ft. - General Observation - 12" VCP

Observations (22)

DistanceCodeObservation
10.2TFDOpen-40% ROOTS
156.9TFOpen
293.6TFActive
180.9MGO12" VCP
159.9TFCCapped
85.3TFDOpen-40% ROOTS
246.9TFOpen
342.4AMH4:05AM
66.7TFCCapped
0AMH3:35AM
290.8TFOpen
209.7TFOpen
250.1TFOpen
79.3TFOpen
303.2TFOpen
0MWM
41.8TFDOpen-80% ROOTS
13.4TFDOpen-90% ROOTS
212.9TFOpen
324.5TFActive
122.9TFDActive-50% ROOTS
0MWL

Properties (3)

custom_field_two
4
customer
LACSD
datetime