Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 3, 2017, 05:07 PM
  • 18 1069_18 1068_132017_091401.mp4

Date
01/03/2017
W/O
0607769
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00682
PipeID
P14927
Time
9:07 AM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7304
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 5
City
LA HABRA HEIGHTS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20170103MI_LA_HABRA_HEIGHTS_TRUNK_SECTION_5
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
18 1069
Downstream MH
18 1068
Dir. of Survey
Downstream
Length Surveyed
281.8 ft.
Total Length
281.8 ft.
Structural Index
3
Structural Quick
4135
Structural Rating
19
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
21
Pipe schematic from manhole 18 1069 to 18 1068
MH: 18 1069MH: 18 1068downstream0 ft. MGO - General Observation - CONNECTION AT MH, 6 OCLOCK, ACTIVE0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 09:10AM0 ft. MWM - Water Mark, 40 %of cross sectional area8.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start21 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6" - Active25.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES87.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active161.6 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES163.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"176.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES198.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES216.3 ft. B - Broken, from 12 to 01 o'clock, within 8 inches of joint: YES232.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"236.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES279.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish281.8 ft. AMH - Downstream Manhole, Survey Ends - 09:45AM

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    8.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    25.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active

    87.7 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    176.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Broken, from 12 to 01 o'clock, within 8 inches of joint: YES

    216.3 ft. - Broken, from 12 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    236.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Downstream Manhole, Survey Ends - 09:45AM

    281.8 ft. - Downstream Manhole, Survey Ends - 09:45AM

Observations (17)

DistanceCodeObservation
161.6CM
236.9FM
0MGOCONNECTION AT MH, 6 OCLOCK, ACTIVE
198.1CM
8.1DAGS
163.1TFA
21TFActive
0MWL
176.5CM
0AMH09:10AM
232.7TFA
216.3B
279.7DAGS
0MWM
281.8AMH09:45AM
87.7TFActive
25.6CM

Properties (4)

additional_info
RFIR INSPECTION ONLY
custom_field_two
2
customer
LACSD
datetime
2017-01-03T09:07:16-08:00