Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2016, 07:22 PM
  • 29 0069_29 0068_1292016_112419.mp4

Date
12/09/2016
W/O
0607759
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z01015
PipeID
P23850
Time
11:22 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7292
Sewer Name
29 EASTSIDE INTERCEPTOR SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
20161209DF_EASTSIDE_INTERCEPTOR_SEWER
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0069
Downstream MH
29 0068
Dir. of Survey
Downstream
Length Surveyed
350.5 ft.
Total Length
350.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole 29 0069 to 29 0068
MH: 29 0069MH: 29 0068downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 11:22 AM0 ft. MWL - Water Level, 10 %of cross sectional area1.6 ft. MGO - General Observation - POSSIBLE STITCHED LINER START 1 O'CLOCK63.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 70% BLOCKED GREASE162.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"180.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4" - OPEN265.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - OPEN268.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 45% BLOCKED GREASE350.5 ft. AMH - Downstream Manhole, Survey Ends - 11:51 AM350.5 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH350.5 ft. MGO - General Observation - ROACHES @ MH350.5 ft. MGO - General Observation - STITCHED LINER @ 2 O'CLOCK

Observation photos (2)

  • General Observation - POSSIBLE STITCHED LINER START 1 O'CLOCK

    1.6 ft. - General Observation - POSSIBLE STITCHED LINER START 1 O'CLOCK

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 70% BLOCKED GREASE

    63.1 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 70% BLOCKED GREASE

Observations (13)

DistanceCodeObservation
350.5AMH11:51 AM
0MWM
162.1TFA
268.3TF45% BLOCKED GREASE
63.1TF70% BLOCKED GREASE
1.6MGOPOSSIBLE STITCHED LINER START 1 O'CLOCK
0AMH11:22 AM
350.5MGOSLIGHT GREASE THROUGHOUT THE REACH
350.5MGOROACHES @ MH
350.5MGOSTITCHED LINER @ 2 O'CLOCK
180.1TBOPEN
265.9TFOPEN
0MWL

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2016-12-09T11:22:03-08:00