Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2016, 08:51 AM
  • 22 0736_22 0713_1212016_025638.mp4

Date
12/01/2016
W/O
0602255
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00821
PipeID
P17092
Time
12:51 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0358
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
SAN DIMAS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
20161201MDM_PUDDINGSTONE_TRUNK_SECTS_1_2
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0736
Downstream MH
22 0713
Dir. of Survey
Downstream
Length Surveyed
328.7 ft.
Total Length
328.7 ft.
Structural Index
3
Structural Quick
4133
Structural Rating
15
O&M Index
4
O&M Quick
5121
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
22
Pipe schematic from manhole 22 0736 to 22 0713
MH: 22 0736MH: 22 0713downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:50AM2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVRE AGG2 ft. MGO - General Observation - MAG COAT 30% START 9:00 TO 3:002.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHES29.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG29.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTCHED29.9 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG54.2 ft. RTJ - Roots Tap Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR62.6 ft. MGO - General Observation - MAG COAT 60% START76.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped79 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG79 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG109 ft. MGO - General Observation - MAG COAT 30% START178.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active280.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active301.1 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SVERE AGG301.1 ft. MWM - Water Mark, 80 %of cross sectional area301.1 ft. MWL - Water Level, 30 %of cross sectional area301.1 ft. MGO - General Observation - MAG COAT FINISH301.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG328.2 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG328.2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active OUTGOING328.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active INCOMING328.2 ft. MGO - General Observation - Conn. @ Mh, 12 O' Clock. OPEN RAGGED STOPLOG IN PLACE328.7 ft. AMH - Downstream Manhole, Survey Ends - 3:25AM

Observation photos (11)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVRE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVRE AGG

  • General Observation - MAG COAT 30% START 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 30% START 9:00 TO 3:00

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHES

    2.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHES

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    29.9 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Roots Tap Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR

    54.2 ft. - Roots Tap Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR

  • General Observation - MAG COAT 60% START

    62.6 ft. - General Observation - MAG COAT 60% START

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    79 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 30% START

    109 ft. - General Observation - MAG COAT 30% START

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SVERE AGG

    301.1 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SVERE AGG

  • Water Mark, 80 %of cross sectional area

    301.1 ft. - Water Mark, 80 %of cross sectional area

  • General Observation - Conn. @ Mh, 12 O' Clock. OPEN RAGGED STOPLOG IN PLACE

    328.2 ft. - General Observation - Conn. @ Mh, 12 O' Clock. OPEN RAGGED STOPLOG IN PLACE

Observations (27)

DistanceCodeObservation
0MWL
178.3TFActive
2.1SSSPEELING CONCRETE SEVERE AGG ATTACHES
29.9SAVSEVERE AGG
0MWM
301.1SAVSVERE AGG
301.1MWM
109MGOMAG COAT 30% START
328.7AMH3:25AM
328.2SAVSEVERE AGG
54.2RTJ
79SAVSEVERE AGG
29.9SSSPEELING CONCRETE SEVERE AGG ATTCHED
301.1MWL
0AMH2:50AM
79SAPSEVERE AGG
301.1MGOMAG COAT FINISH
29.9SAMSEVERE AGG
280.9TFActive
301.1SAPSEVERE AGG
76.3TFCapped
2SAMSEVRE AGG
328.2MGOConn. @ Mh, 9 O' Clock. Active OUTGOING
2MGOMAG COAT 30% START 9:00 TO 3:00
328.2MGOConn. @ Mh, 3 O' Clock. Active INCOMING
328.2MGOConn. @ Mh, 12 O' Clock. OPEN RAGGED STOPLOG IN PLACE
62.6MGOMAG COAT 60% START

Properties (4)

custom_field_three
SOME PEELING CONCRETE-MISSING SEVERE AGG
custom_field_two
2
customer
LACSD
datetime
2016-12-01T00:51:17-08:00