Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 22, 2016, 09:47 AM
  • C 0566_C 0565_11222016_015132.mp4

Date
11/22/2016
W/O
0602265
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00362
PipeID
P04750
Time
1:47 AM
Certificate
U-104-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0352
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LAKEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
20161121MDM_JOINT_OUTFALL_C_UNIT_4D
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Upstream MH
C 0566
Downstream MH
C 0565
Dir. of Survey
Downstream
Length Surveyed
418.3 ft.
Total Length
418.3 ft.
Structural Index
3
Structural Quick
3A23
Structural Rating
36
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
42
Pipe schematic from manhole C 0566 to C 0565
MH: C 0566MH: C 0565downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active7 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SLIGHT14 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - ROCKS21.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE30.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE30.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT33 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - ROCKS48.1 ft. MGO - General Observation - 27" VCP53.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - ROCKS98.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT114.6 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - SL119.1 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE130.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H137.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H226 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H235 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H235 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - SL239.2 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish - SL243.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Change - H266.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H270.3 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - H271.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES278.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H331.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES331.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active371.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H391.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H418.3 ft. AMH - Downstream Manhole, Survey Ends - 2:45AM

Observation photos (7)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    21.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    30.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • General Observation - 27" VCP

    48.1 ft. - General Observation - 27" VCP

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - SL

    114.6 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - SL

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    130.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    226 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - SL

    235 ft. - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - SL

Observations (32)

DistanceCodeObservation
0MWM
48.1MGO27" VCP
331.5DAGS
130.5FLH
0AMH1:55AM
53.9DSZROCKS
119.1FCHAIRLINE
0MGOConn. @ Mh, 9 O' Clock. OPEN
391.9FLH
418.3AMH2:45AM
271.4FL
30.9FLHAIRLINE
266.9FLH
270.3FCH
0MWL
243.1FLH
226FLH
33DSZROCKS
0MGOConn. @ Mh, 3 O' Clock. Active
114.6FLSL
137.2FLH
239.2FSSL
98.3FLSLIGHT
235FLH
278.3FLH
7FCSLIGHT
14DSZROCKS
21.3FLHAIRLINE
331.5TFActive
235FSSL
30.9FLSLIGHT
371.8FLH

Properties (4)

custom_field_three
LONG SLIGHT JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-11-22T01:47:15-08:00