Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2016, 04:06 PM
  • 05 1368_05 1422_11172016_081036.mp4

Date
11/17/2016
W/O
0602258
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00444
PipeID
P06586
Time
8:06 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7277
Sewer Name
05 GARDENA PUMP TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Capital Improvement Program Assesment
Project
20161117AM_GARDENA_PUMP_TRUNK
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
05 1368
Downstream MH
05 1422
Dir. of Survey
Downstream
Length Surveyed
304.1 ft.
Total Length
304.1 ft.
Structural Index
3
Structural Quick
3A2A
Structural Rating
55
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
58
Pipe schematic from manhole 05 1368 to 05 1422
MH: 05 1368MH: 05 1422downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. AMH - Upstream Manhole, Survey Begins - 8:09 AM2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"12.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start22.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish38.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES43.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES46.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES56.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start59.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES82.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish83.5 ft. TBD - Tap Break-In Defective, at 12 o'clock, -, , within 8 inches of joint: NO, 4" - ACTIVE, BROKEN85.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"87.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES97.4 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES100.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES130.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES130.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES134.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"136 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES138.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES138.6 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES138.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start148.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish179.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN185.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN210.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES217.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES223.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES225.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start236.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN253.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish288 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"303.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish303.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish303.9 ft. MGO - General Observation - ROACHES INSIDE THE MH.303.9 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK303.9 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK304.1 ft. AMH - Downstream Manhole, Survey Ends - 8:53 AM

Observation photos (11)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    46.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    56.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    59.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Tap Break-In Defective, at 12 o'clock, -,  , within 8 inches of joint: NO, 4" - ACTIVE, BROKEN

    83.5 ft. - Tap Break-In Defective, at 12 o'clock, -, , within 8 inches of joint: NO, 4" - ACTIVE, BROKEN

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    97.4 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    130.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Hole, at 12 o'clock, within 8 inches of joint: YES

    138.6 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    179.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    223.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (43)

DistanceCodeObservation
38.4CL
56.6CL
43.7CL
210.4CL
225.6CL
134.3TFA
0MWL
46.2CL
6.5TFA
303.9MGOROACHES INSIDE THE MH.
130.8FL
85.6TFC
148.7CL
217.9CL
185.6TFOPEN
138.6FL
0MWM
138.6H
236.8TFOPEN
303.9MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
303.8SSS
303.9MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
253.8CL
87.1FL
304.1AMH8:53 AM
130.8FL
2SAV
2SSS
303.8SAV
136CM
82.1CL
138.6CL
100.1CL
22.9CL
97.4FL
223.1FL
179.5FLPOSSIBLY BROKEN
0MGOROACHES INSIDE THE MH.
59.2FL
12.9CL
0AMH8:09 AM
83.5TBDACTIVE, BROKEN
288TFC

Properties (5)

additional_info
RFIR INSPECTION ONLY
custom_field_three
POSSIBLE BROKEN PIPE & A HOLE IN THE JOINT
custom_field_two
1
customer
LACSD
datetime
2016-11-17T08:06:08-08:00