Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 16, 2016, 08:30 AM
  • 02 1139_02 1138_11162016_010318.mp4

Date
11/16/2016
W/O
0607058
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00351
PipeID
P02922
Time
12:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0344
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Maintenance Related
Project
20161115MDM_GARFIELD_AVENUE_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1139
Downstream MH
02 1138
Dir. of Survey
Downstream
Length Surveyed
305.5 ft.
Total Length
305.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2212
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 1139 to 02 1138
MH: 02 1139MH: 02 1138downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:00AM0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area16.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped85.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped102.9 ft. RTJ - Roots Tap Joint, from 03 to 05 o'clock, 4 %, within 8 inches of joint: YESR106.6 ft. MGO - General Observation - 15" VCP132.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped180.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-100% ROOTS180.3 ft. RFL - Roots Fine Lateral, from 08 to 10 o'clock - 8%202 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YESR - 1%227.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped271.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped290.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped305 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN305.5 ft. AMH - Downstream Manhole, Survey Ends - 1:25AM

Observation photos (1)

  • General Observation - 15" VCP

    106.6 ft. - General Observation - 15" VCP

Observations (16)

DistanceCodeObservation
180.3TFDOpen-100% ROOTS
305MGOConn. @ Mh, 3 O' Clock. OPEN
102.9RTJ
271.1TFCCapped
305.5AMH1:25AM
106.6MGO15" VCP
290.5TFCCapped
0AMH1:00AM
180.3RFL8%
202RFJ1%
16.6TFCCapped
0MWM
0MWL
132.7TFCCapped
85.2TFCCapped
227.5TFCCapped

Properties (4)

additional_info
ROOT & GREASE EVALUATION
custom_field_two
4
customer
LACSD
datetime
2016-11-16T00:30:04-08:00