- Date
- 10/31/2016
- W/O
- 0596965
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00665
- PipeID
- P13368
- Time
- 4:15 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6758
- Sewer Name
- 16 SAN MARINO OUTFALL TRUNK
- City
- SAN MARINO
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 16
- Page No.
- 17
- Purpose
- Capital Improvement Program Assesment
- Project
- 20161031MDM_SAN_MARINO_OUTFALL_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Upstream MH
- 16 0317
- Downstream MH
- 16 0316
- Dir. of Survey
- Downstream
- Length Surveyed
- 366.6 ft.
- Total Length
- 366.6 ft.
- Structural Index
- 2
- Structural Quick
- 4134
- Structural Rating
- 38
- O&M Index
- 2
- O&M Quick
- 2100
- O&M Rating
- 2
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 40
Pipe schematic from manhole 16 0317 to 16 0316 Observation photos (4)

80.1 ft. - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - SECTION OF BRICK

340.2 ft. - General Observation - 18" VCP

358.6 ft. - Fracture Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT

361.2 ft. - Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT