- Date
- 10/18/2016
- W/O
- 0601708
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00471
- PipeID
- P06990
- Time
- 2:45 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6738
- Sewer Name
- 05 LOMITA TRUNK
- City
- LOMITA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 32
- Purpose
- Maintenance Related
- Project
- 20161018MDM_LOMITA_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 21 in.
- Upstream MH
- 05 1762
- Downstream MH
- 05 1761
- Dir. of Survey
- Downstream
- Length Surveyed
- 397.8 ft.
- Total Length
- 397.8 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 3
- O&M Quick
- 5141
- O&M Rating
- 13
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 13
Pipe schematic from manhole 05 1762 to 05 1761 Observation photos (5)

8.1 ft. - General Observation - 21" VCP

102.3 ft. - Water Mark, 90 %of cross sectional area

192.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES

239.2 ft. - Water Mark, 40 %of cross sectional area

321.4 ft. - Water Level, 5 %of cross sectional area