Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 18, 2016, 04:13 PM
  • 16 0348_16 0347_10182016_092929.mp4

Date
10/18/2016
W/O
0596965
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00665
PipeID
P13399
Time
9:13 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7252
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20161018AM_SAN_MARINO_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
16 0348
Downstream MH
16 0347
Dir. of Survey
Downstream
Length Surveyed
200.3 ft.
Total Length
200.3 ft.
Structural Index
4
Structural Quick
544B
Structural Rating
75
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
75
Pipe schematic from manhole 16 0348 to 16 0347
MH: 16 0348MH: 16 0347downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 9:30 AM0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. MWL - Water Level, 25 %of cross sectional area5.6 ft. B - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES7.1 ft. B - Broken, from 11 to 12 o'clock, within 8 inches of joint: YES12.5 ft. B - Broken, from 01 to 02 o'clock, within 8 inches of joint: YES17.4 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN19.7 ft. FM - Fracture Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES22.4 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN27.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES30.1 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN32.8 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES35.1 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES37.6 ft. B - Broken, from 12 to 03 o'clock, within 8 inches of joint: YES40 ft. FM - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES42.6 ft. FM - Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES52.8 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN55.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start55.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start66.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.3 ft. B - Broken, from 11 to 03 o'clock, within 8 inches of joint: YES105.2 ft. MGO - General Observation - CHIPPING117.8 ft. B - Broken, from 10 to 12 o'clock, within 8 inches of joint: YES134.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"198.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish198.1 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH198.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish198.6 ft. MGO - General Observation - UNKNOWN CONN. INSIDE THE MH. @ 03 O'CLOCK198.6 ft. MGO - General Observation - ROACHES INSIDE THE MH.200.3 ft. AMH - Downstream Manhole, Survey Ends - 10:10 AM

Observation photos (18)

  • Broken, from 01 to 04 o'clock, within 8 inches of joint: YES

    5.6 ft. - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 11 to 12 o'clock, within 8 inches of joint: YES

    7.1 ft. - Broken, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Broken, from 01 to 02 o'clock, within 8 inches of joint: YES

    12.5 ft. - Broken, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    17.4 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Fracture Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES

    19.7 ft. - Fracture Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    22.4 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    27.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    30.1 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    32.8 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    35.1 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 12 to 03 o'clock, within 8 inches of joint: YES

    37.6 ft. - Broken, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    40 ft. - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

    42.6 ft. - Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    52.8 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    55.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 11 to 03 o'clock, within 8 inches of joint: YES

    95.3 ft. - Broken, from 11 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - CHIPPING

    105.2 ft. - General Observation - CHIPPING

  • Broken, from 10 to 12 o'clock, within 8 inches of joint: YES

    117.8 ft. - Broken, from 10 to 12 o'clock, within 8 inches of joint: YES

Observations (31)

DistanceCodeObservation
12.5B
198.6MGOUNKNOWN CONN. INSIDE THE MH. @ 03 O'CLOCK
105.2MGOCHIPPING
22.4FMPOSSIBLY BROKEN
0MWM
7.1B
198.6MGOROACHES INSIDE THE MH.
35.1FM
17.4FMPOSSIBLY BROKEN
117.8B
198.1CM
5.6B
52.8FMPOSSIBLY BROKEN
198.1MGOSLIGHT GREASE THROUGHOUT THE REACH
55.1CM
32.8FM
30.1FMPOSSIBLY BROKEN
66.8TFC
0AMH9:30 AM
95.3B
27.6FM
37.6B
40FM
134.3TFC
55.1FM
198.1FM
19.7FM
0MGOROACHES INSIDE THE MH.
200.3AMH10:10 AM
42.6FM
0MWL

Properties (5)

additional_info
RFIR INSPECTION
custom_field_three
BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-10-18T09:13:44-07:00