Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 3, 2016, 08:08 PM
  • C 0246_C 0245_1032016_131329.mp4

Date
10/03/2016
W/O
0591689
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00928
PipeID
P20307
Time
1:08 PM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0307
Sewer Name
C JOINT OUTFALL C - UNIT 6A
City
LONG BEACH
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20161003AM_JOINT_OUTFALL_C_UNIT_6A
Material
NRCP
Shape
Circular
Height
21 in.
Upstream MH
C 0246
Downstream MH
C 0245
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
4
O&M Quick
4131
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole C 0246 to C 0245
MH: C 0246MH: C 0245downstream0 ft. MWL - Water Level, 100 %of cross sectional area0 ft. MGO - General Observation - CORRODED CHANNEL0 ft. AMH - Upstream Manhole, Survey Begins - 1:12 PM2 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO2 ft. SMW - Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: NO - POSSIBLE2 ft. LD - Alignment Down, 45 %2 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: NO2.1 ft. MSA - Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

Observation photos (6)

  • Water Level, 100 %of cross sectional area

    0 ft. - Water Level, 100 %of cross sectional area

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: NO - POSSIBLE

    2 ft. - Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: NO - POSSIBLE

  • Deposits Attached Grease, 15 %of cross sectional area, from 10 to 02 o'clock,  , within 8 inches of joint: NO

    2 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: NO

  • Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

    2.1 ft. - Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

Observations (9)

DistanceCodeObservation
2SAV
2SSS
2SMWPOSSIBLE
2LD
0MWL
0MGOCORRODED CHANNEL
2.1MSAVIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
2DAGS
0AMH1:12 PM

Properties (6)

additional_info
RFIR INSPECTION, VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
custom_field_three
POSSIBLE MISSING WALL
custom_field_two
1
customer
LACSD
datetime
2016-10-03T13:08:27-07:00
year_laid
19530407