Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2016, 08:56 AM
Date
09/14/2016
W/O
0585843
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00226
PipeID
P02110
Time
1:56 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0276
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
SOUTH GATE
Loc. details
Railway
Location Code
L
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
20190914VMR_WILCOX_AVENUE_TRUNK_EXTENSION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Upstream MH
01 1198
Downstream MH
01 1155
Dir. of Survey
Downstream
Length Surveyed
90.2 ft.
Total Length
90.2 ft.
Structural Index
2
Structural Quick
3423
Structural Rating
25
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
25
Pipe schematic from manhole 01 1198 to 01 1155
MH: 01 1198MH: 01 1155downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05:25 AM0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area11.6 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES11.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES15.2 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES17.9 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES21.6 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES24.1 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES27.7 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES30.2 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES33.3 ft. CC - Crack Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES36.6 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES38.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"38.8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES42.4 ft. CC - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES45.2 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES47.9 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES72.7 ft. MMC - Material Change, Cast Iron88.4 ft. MMC - Material Change, Vitrified clay pipe90.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 15"90.2 ft. AMH - Downstream Manhole, Survey Ends - 05:58 AM

Observation photos (2)

  • Material Change, Cast Iron

    72.7 ft. - Material Change, Cast Iron

  • Material Change, Vitrified clay pipe

    88.4 ft. - Material Change, Vitrified clay pipe

Observations (22)

DistanceCodeObservation
24.1CC
0AMH05:25 AM
38.8CL
33.3CC
90.2TF
0MWM
47.9CM
42.4CC
11.6CL
45.2CC
0MWL
38.4TFC
30.2CC
27.7CM
17.9CM
72.7MMC
11.6CL
15.2CM
90.2AMH05:58 AM
21.6CC
36.6CC
88.4MMC

Properties (3)

custom_field_two
2
customer
LACSD
datetime
2016-09-14T01:56:09-07:00