Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 26, 2016, 09:00 AM
  • 19 0239_19 0238_9262016_040652.mp4

Date
09/26/2016
W/O
0585465
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00728
PipeID
P15209
Time
2:00 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7241
Sewer Name
19 STUDEBAKER ROAD TRUNK
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
20160926MDM_STUDEBAKER_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
19 0239
Downstream MH
19 0238
Dir. of Survey
Downstream
Length Surveyed
349.9 ft.
Total Length
349.9 ft.
Structural Index
3
Structural Quick
4131
Structural Rating
9
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 19 0239 to 19 0238
MH: 19 0239MH: 19 0238downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:05AM8 ft. MGO - General Observation - 15" VCP21.8 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE41 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped88.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped142.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped189.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped243.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped314.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open339.4 ft. MWM - Water Mark, 60 %of cross sectional area339.4 ft. MWL - Water Level, 40 %of cross sectional area343.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 03 o'clock, , within 8 inches of joint: YES343.1 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - HAIRLINE349.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT349.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. STUB349.9 ft. AMH - Downstream Manhole, Survey Ends - 4:40AM

Observation photos (2)

  • General Observation - 15" VCP

    8 ft. - General Observation - 15" VCP

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    349.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

Observations (19)

DistanceCodeObservation
189.5TFCCapped
314.4TFOpen
0MWM
243.2TFCCapped
339.4MWM
343.1DAE
0MGOConn. @ Mh, 9 O' Clock. Active
142.2TFCCapped
8MGO15" VCP
349.5MGOConn. @ Mh, 3 O' Clock. STUB
339.4MWL
0MWL
21.8FCHAIRLINE
0AMH4:05AM
88.7TFCCapped
349.4FMSLIGHT
41TFCCapped
343.1FLHAIRLINE
349.9AMH4:40AM

Properties (4)

custom_field_three
ONE AREA MULTIPLE SLIGHT
custom_field_two
3
customer
LACSD
datetime
2016-09-26T02:00:56-07:00