Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 19, 2016, 10:27 AM
  • 05 0880_05 0879_9192016_035808.mp4

Date
09/19/2016
W/O
0585472
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00457
PipeID
P06111
Time
3:27 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0284
Sewer Name
05 IMPERIAL HIGHWAY EXTENSION TRUNK
City
LENNOX
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
09
Purpose
Routine Assessment
Project
20160919MDM_IMPERIAL_HIGHWAY_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 0880
Downstream MH
05 0879
Dir. of Survey
Downstream
Length Surveyed
321.7 ft.
Total Length
321.7 ft.
Structural Index
2
Structural Quick
332A
Structural Rating
30
O&M Index
4
O&M Quick
4200
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
38
Pipe schematic from manhole 05 0880 to 05 0879
MH: 05 0880MH: 05 0879downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 2 O' Clock. STUB0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock.OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 4:00AM0 ft. MWM - Water Mark, 30 %of cross sectional area9.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE104.1 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H104.1 ft. MWM - Water Mark, 50 %of cross sectional area104.1 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H111.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped114.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped124.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H148.2 ft. MGO - General Observation - 10" VCP152.1 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H152.1 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H173.3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H173.3 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H188.5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H194.6 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES203.7 ft. CC - Crack Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES216.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open218.7 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H219.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped255 ft. MWM - Water Mark, 70 %of cross sectional area278.9 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H318.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H321.7 ft. AMH - Downstream Manhole, Survey Ends - 4:35AM

Observation photos (2)

  • General Observation - 10" VCP

    148.2 ft. - General Observation - 10" VCP

  • Water Mark, 70 %of cross sectional area

    255 ft. - Water Mark, 70 %of cross sectional area

Observations (27)

DistanceCodeObservation
219.5TFCCapped
194.6CL
148.2MGO10" VCP
9.2FLHAIRLINE
124.4FLH
152.1FCH
173.3FCH
216.9TFOpen
203.7CC
114.8TFCCapped
111.1TFCCapped
0MWL
0MGOConn. @ Mh, 2 O' Clock. STUB
104.1FCH
218.7FCH
173.3FCH
318.9FLH
152.1FCH
321.7AMH4:35AM
0MGOConn. @ Mh, 3 O' Clock.OPEN
188.5FCH
255MWM
278.9FCH
104.1MWM
0AMH4:00AM
104.1FCH
0MWM

Properties (4)

custom_field_three
HAIRLINES
custom_field_two
4
customer
LACSD
datetime
2016-09-19T03:27:22-07:00