Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2016, 07:43 AM
Date
09/02/2016
W/O
0591702
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00013
PipeID
P00370
Time
12:43 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0265
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
20160902VMR_KEYSTONE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0322
Downstream MH
08 0321A
Dir. of Survey
Downstream
Length Surveyed
71.6 ft.
Total Length
71.6 ft.
Structural Index
2
Structural Quick
3127
Structural Rating
20
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
20
Pipe schematic from manhole 08 0322 to 08 0321A
MH: 08 0322MH: 08 0321Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 03:55 AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area5.8 ft. CC - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES5.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES5.8 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES8.6 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES8.6 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES12.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES12.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES14.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start14.1 ft. CC - Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES14.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start31.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"47.1 ft. CC - Crack Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES70.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish70.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish71 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 10"71.6 ft. AMH - Downstream Manhole, Survey Ends - 04:30 AM

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    5.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
70.4CL
14.1CL
8.6CL
12.1CL
47.1CC
70.4CL
5.8CC
14.1CC
5.8CM
12.1CL
0AMH03:55 AM
0MWM
71.6AMH04:30 AM
5.8CL
14.1CL
71TFA
8.6CL
31.4TFC
0MWL

Properties (3)

custom_field_two
2
customer
LACSD
datetime