Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2016, 09:35 AM
  • 19 0258_19 0257_8302016_030707.mp4

Date
08/30/2016
W/O
0585465
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00728
PipeID
P15228
Time
2:35 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0260
Sewer Name
19 STUDEBAKER ROAD TRUNK
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
01
Purpose
Routine Assessment
Project
20160829MDM_STUDEBAKER_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
19 0257
Downstream MH
19 0258
Dir. of Survey
Upstream
Length Surveyed
326.8 ft.
Total Length
326.8 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 19 0257 to 19 0258
MH: 19 0257MH: 19 0258upstream0 ft. AMH - Upstream Manhole, Survey Ends - 3:25AM54.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped102.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped156.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped183.9 ft. MGO - General Observation - 15" VCP204.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped208 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SLIGHT240.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open251.5 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE252.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped300.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped326.8 ft. AMH - Downstream Manhole, Survey Begins - 2:55AN326.8 ft. MWL - Water Level, 5 %of cross sectional area326.8 ft. MWM - Water Mark, 15 %of cross sectional area

Observations (14)

DistanceCodeObservation
142.9MGO15" VCP
0AMH2:55AN
75.3FCHAIRLINE
224.7TFCCapped
0MWL
122.2TFCCapped
0MWM
26.6TFCCapped
170.5TFCCapped
118.8FCSLIGHT
74.4TFCCapped
86.6TFOpen
272.4TFCCapped
326.8AMH3:25AM

Properties (4)

custom_field_three
HAIRLINE FRACTURE
custom_field_two
4
customer
LACSD
datetime
2016-08-30T02:35:10-07:00