Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 27, 2016, 08:05 AM
  • 19 0234_19 0233_8272016_022424.mp4

Date
08/27/2016
W/O
0585415
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00729
PipeID
P15204
Time
1:05 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HO256
Sewer Name
19 WEST ARTESIA TRUNK
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
01
Purpose
Routine Assessment
Project
20160827MDM_WEST_ARTESIA_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
19 0234
Downstream MH
19 0233
Dir. of Survey
Downstream
Length Surveyed
285.1 ft.
Total Length
285.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 19 0234 to 19 0233
MH: 19 0234MH: 19 0233downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:20AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active8 ft. MGO - General Observation - 12" VCP18.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped51.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped100.3 ft. MWM - Water Mark, 30 %of cross sectional area145 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - HAIRLINE146.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active151 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active261.1 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6" - Open 60% ROOTS263.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped263.4 ft. MWM - Water Mark, 20 %of cross sectional area263.4 ft. MWL - Water Level, 5 %of cross sectional area285.1 ft. AMH - Downstream Manhole, Survey Ends - 12:50AM

Observation photos (2)

  • General Observation - 12" VCP

    8 ft. - General Observation - 12" VCP

  • Water Mark, 30 %of cross sectional area

    100.3 ft. - Water Mark, 30 %of cross sectional area

Observations (16)

DistanceCodeObservation
8MGO12" VCP
0MWM
0MWL
151TFActive
263.4TFCCapped
263.4MWM
285.1AMH12:50AM
18.1TFCCapped
0AMH12:20AM
51.5TFCCapped
0MGOConn. @ Mh, 9 O' Clock. Active
146.3TFActive
261.1TBDOpen 60% ROOTS
100.3MWM
263.4MWL
145FLHAIRLINE

Properties (3)

custom_field_two
4
customer
LACSD
datetime