Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2016, 10:40 AM
  • 21 0651_21 0650_8252016_035428.mp4

Date
08/25/2016
W/O
0585474
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00767
PipeID
P15804
Time
3:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0254
Sewer Name
21 FIRST ST TR, SECT 1A & CONNS TO 1ST ST TR SYSTM
City
POMONA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
14
Purpose
Routine Assessment
Project
20160825MDM_FRIST_ST_TR_SECT_1A_CONNS_TO_ST_TR_SYSTM
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
21 0651
Downstream MH
21 0650
Dir. of Survey
Downstream
Length Surveyed
354.7 ft.
Total Length
354.7 ft.
Structural Index
5
Structural Quick
5A32
Structural Rating
61
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
61
Pipe schematic from manhole 21 0651 to 21 0650
MH: 21 0651MH: 21 0650downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:50AM2 ft. MGO - General Observation - MAG COAT 100% START 8:00 TO 4:0027.4 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR28.3 ft. SAV - Surface Aggregate Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG69.5 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR77.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped85.9 ft. SAV - Surface Aggregate Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG85.9 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR89.2 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR89.2 ft. MGO - General Observation - MAG COAT 99% START112 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR113 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR124.9 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR132.9 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO174.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped184.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open270.7 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR308.1 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR325.6 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM354.3 ft. MGO - General Observation - MAG COAT 99% FINISH354.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active354.7 ft. AMH - Downstream Manhole, Survey Ends - 4:35AM

Observation photos (13)

  • General Observation - MAG COAT 100% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 100% START 8:00 TO 4:00

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

    27.4 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

  • Surface Aggregate Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

    28.3 ft. - Surface Aggregate Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    69.5 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

    85.9 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

    89.2 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

    112 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

    113 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

    124.9 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO

    132.9 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    270.7 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    308.1 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM

    325.6 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM

Observations (24)

DistanceCodeObservation
28.3SAVSEVERE AGG
0MWM
27.4SRVCIRCUM LONG REBAR
184.4TBOpen
354.3MGOMAG COAT 99% FINISH
77.5TFCCapped
85.9SAVSEVERE AGG
0MWL
174.4TFCCapped
85.9SRVCIRCUM LONG REBAR
0AMH3:50AM
89.2SRVCIRCUM LONG REBAR
113SRVCIRCUM LONG REBAR
124.9SRVCIRCUM LONG REBAR
69.5SRVCIRCUM REBAR
354.3MGOConn. @ Mh, 3 O' Clock. Active
308.1SRVCIRCUM REBAR
354.7AMH4:35AM
132.9SRV
112SRVLONG REBAR
2MGOMAG COAT 100% START 8:00 TO 4:00
89.2MGOMAG COAT 99% START
325.6SRVCIRCUM
270.7SRVCIRCUM REBAR

Properties (4)

custom_field_three
99% MAG COAT-CIRCUM LONG REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime