Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2016, 09:16 AM
  • 05 0462_05 0461_8242016_032912.mp4

Date
08/24/2016
W/O
0585478
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00526
PipeID
P05677
Time
2:16 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0253
Sewer Name
05 STRAWBERRY AVENUE TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
20160824MDM_STRAWBERRY_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
05 0462
Downstream MH
05 0461
Dir. of Survey
Downstream
Length Surveyed
201.7 ft.
Total Length
201.7 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
9
O&M Index
3
O&M Quick
4323
O&M Rating
18
Overall Index
3
Overall Quick
Overall Rating
27
Pipe schematic from manhole 05 0462 to 05 0461
MH: 05 0462MH: 05 0461downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:10AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 6 O' Clock. Active3 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT49.5 ft. MGO - General Observation - 12" VCP49.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open65 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES75 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open87.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped125.3 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES125.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped127.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open139.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE155.3 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - ROCKS167 ft. MWM - Water Mark, 60 %of cross sectional area175.2 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H176 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped176.9 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - ROCKS178.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open178.7 ft. MWM - Water Mark, 50 %of cross sectional area201.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active201.1 ft. MGO - General Observation - Conn. @ Mh, 12 O' Clock. OPEN201.7 ft. AMH - Downstream Manhole, Survey Ends - 3:45AM

Observation photos (1)

  • General Observation - 12" VCP

    49.5 ft. - General Observation - 12" VCP

Observations (25)

DistanceCodeObservation
167MWM
155.3DSGVROCKS
75TFOpen
0MWL
176.9DSGVROCKS
49.5MGO12" VCP
49.5TFOpen
0AMH3:10AM
201.1MGOConn. @ Mh, 3 O' Clock. Active
0MWM
125.3DSGV
178.7TFOpen
176TFCCapped
65DSGV
127.8TFOpen
139.7FLHAIRLINE
87.4TFCCapped
201.7AMH3:45AM
125.3TFCapped
175.2FCH
3FCSLIGHT
178.7MWM
201.1MGOConn. @ Mh, 12 O' Clock. OPEN
0MGOConn. @ Mh, 6 O' Clock. Active
3FCSLIGHT

Properties (4)

custom_field_three
FEW SLIGHT FRACTURES
custom_field_two
4
customer
LACSD
datetime
2016-08-24T02:16:52-07:00