Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 21, 2016, 05:03 PM
  • 19 0037_19 0036_8212016_100704.mp4

Date
08/21/2016
W/O
0585475
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00725
PipeID
P15067
Time
10:03 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7211
Sewer Name
19 FULLERTON ROAD TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary
District
District 19
Page No.
09
Purpose
Routine Assessment
Project
20160821AM_FULLERTON_ROAD_TRUNK_PART_3
Material
Vitrified Clay Pipe
Shape
Other
Height
12 in.
Upstream MH
19 0037
Downstream MH
19 0036
Dir. of Survey
Downstream
Length Surveyed
330 ft.
Total Length
330 ft.
Structural Index
3
Structural Quick
5236
Structural Rating
37
O&M Index
2
O&M Quick
2B00
O&M Rating
26
Overall Index
2
Overall Quick
Overall Rating
63
Pipe schematic from manhole 19 0037 to 19 0036
MH: 19 0037MH: 19 0036downstream0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. AMH - Upstream Manhole, Survey Begins - 10:06 AM0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area6.8 ft. CM - Crack Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES6.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES21.9 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES21.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: YES33.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"34.7 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 10 to 04 o'clock, , within 8 inches of joint: YES44.7 ft. CC - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES69.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES80 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES80 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES81.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"82.5 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES92.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES92.6 ft. CM - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES108 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES108 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES122.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES128 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 02 o'clock, , within 8 inches of joint: YES128 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES133.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES134.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"135.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: YES140.9 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES150.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start182.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"183.7 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES188.7 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES214 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start230.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"283.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"299.7 ft. B - Broken, from 01 to 03 o'clock, within 8 inches of joint: YES319.9 ft. B - Broken, from 08 to 02 o'clock, within 8 inches of joint: YES329.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish329.7 ft. MGO - General Observation - SLIGHT GREASE/DEBRIS/CALCIUM THROUGHOUT THE REACH329.8 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK329.8 ft. MGO - General Observation - ROACHES INSIDE THE MH.329.8 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK330 ft. AMH - Downstream Manhole, Survey Ends - 10:42 AM

Observation photos (8)

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 10 to 04 o'clock,  , within 8 inches of joint: YES

    34.7 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 10 to 04 o'clock, , within 8 inches of joint: YES

  • Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES

    44.7 ft. - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 11 o'clock,  , within 8 inches of joint: YES

    80 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    82.5 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock,  , within 8 inches of joint: YES

    133.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    140.9 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Broken, from 01 to 03 o'clock, within 8 inches of joint: YES

    299.7 ft. - Broken, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 02 o'clock, within 8 inches of joint: YES

    319.9 ft. - Broken, from 08 to 02 o'clock, within 8 inches of joint: YES

Observations (43)

DistanceCodeObservation
80DAE
329.8MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
0MGOROACHES INSIDE THE MH.
183.7CM
80CL
0AMH10:06 AM
329.8MGOROACHES INSIDE THE MH.
128DAE
329.7CM
21.9CM
69.9CL
329.7DAE
108DAE
134.5TFC
299.7B
230.5TFC
81.3TFC
92.6DAE
182.5TFC
82.5DAE
44.7CC
0MWL
6.8CM
108CM
34.7DAE
33.3TFC
92.6CM
128CL
283.5TFC
319.9B
329.7MGOSLIGHT GREASE/DEBRIS/CALCIUM THROUGHOUT THE REACH
122.8DAE
214CM
133.1DAE
21.9DAE
140.9DAE
0MWM
330AMH10:42 AM
6.8DAE
188.7CL
135.8DAE
150.7DAE
329.8MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK

Properties (4)

custom_field_three
BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-08-21T10:03:03-07:00