Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 18, 2016, 03:50 PM
  • 01 0206_01 0205_8182016_104247.mp4

Date
08/18/2016
W/O
0586813
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00202
PipeID
P01248
Time
8:50 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7207
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20160818AM_COMPTON_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
01 0206
Downstream MH
01 0205
Dir. of Survey
Downstream
Length Surveyed
341.5 ft.
Total Length
341.5 ft.
Structural Index
3
Structural Quick
5144
Structural Rating
43
O&M Index
2
O&M Quick
4125
O&M Rating
14
Overall Index
3
Overall Quick
Overall Rating
57
Pipe schematic from manhole 01 0206 to 01 0205
MH: 01 0206MH: 01 0205downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 10:41 AM0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. MGO - General Observation - ROACHES INSIDE THE MH.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start15.2 ft. B - Broken, from 09 to 01 o'clock, within 8 inches of joint: YES15.2 ft. MGP - General Photograph - BROKEN29.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES40.3 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN41.9 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 60% BLOCKED77.4 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 50% BLOCKED82.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 90% BLOCKED119.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES121.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN136.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN167.3 ft. MWL - Water Level, 50 %of cross sectional area167.3 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6", 6" - UNKNOWN, 95% BLOCKED205.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN221.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN240.6 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN260 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"267.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"270.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN281.9 ft. FM - Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES319 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 20% BLOCKED322.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish322.8 ft. MGO - General Observation - SEVERE CHIPPING322.8 ft. MMC - Material Change, Vitrified clay pipe322.8 ft. FM - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES322.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish329.1 ft. CM - Crack Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES331.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES337.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES337.8 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES340.8 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH340.8 ft. MGO - General Observation - MODERATE DEBRIS THROUGHOUT THE REACH340.9 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 12 O'CLOCK340.9 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK341.2 ft. MGO - General Observation - ROACHES INSIDE THE MH.341.5 ft. AMH - Downstream Manhole, Survey Ends - 11:22 AM

Observation photos (17)

  • Water Level, 40 %of cross sectional area

    0 ft. - Water Level, 40 %of cross sectional area

  • Broken, from 09 to 01 o'clock, within 8 inches of joint: YES

    15.2 ft. - Broken, from 09 to 01 o'clock, within 8 inches of joint: YES

  • General Photograph - BROKEN

    15.2 ft. - General Photograph - BROKEN

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    29.3 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    40.3 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 60% BLOCKED

    41.9 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 60% BLOCKED

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 50% BLOCKED

    77.4 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 50% BLOCKED

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 90% BLOCKED

    82.6 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 90% BLOCKED

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    119.8 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Water Level, 50 %of cross sectional area

    167.3 ft. - Water Level, 50 %of cross sectional area

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6", 6" - UNKNOWN, 95% BLOCKED

    167.3 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6", 6" - UNKNOWN, 95% BLOCKED

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    240.6 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

    281.9 ft. - Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 20% BLOCKED

    319 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 20% BLOCKED

  • General Observation - SEVERE CHIPPING

    322.8 ft. - General Observation - SEVERE CHIPPING

  • Material Change, Vitrified clay pipe

    322.8 ft. - Material Change, Vitrified clay pipe

  • Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    322.8 ft. - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

Observations (42)

DistanceCodeObservation
322.8SSS
341.2MGOROACHES INSIDE THE MH.
29.3FL
0MWL
340.8MGOSLIGHT GREASE THROUGHOUT THE REACH
167.3MWL
322.8MGOSEVERE CHIPPING
15.2B
0MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
337.8CM
119.8FL
40.3FMPOSSIBLY BROKEN
77.4TFDOPEN, 50% BLOCKED
267.7TFA
270.3TFOPEN
221.2TFOPEN
41.9TFDOPEN, 60% BLOCKED
322.8MMC
15.2MGPBROKEN
331.9CL
240.6FMPOSSIBLY BROKEN
322.8FM
136.6TFOPEN
329.1CM
281.9FM
82.6TFDOPEN, 90% BLOCKED
260TFA
341.5AMH11:22 AM
121.3TFOPEN
340.8MGOMODERATE DEBRIS THROUGHOUT THE REACH
0AMH10:41 AM
2SSS
205.9TFOPEN
340.9MGOCAPPED CONN. INSIDE THE MH. @ 12 O'CLOCK
0MWM
167.3TFDUNKNOWN, 95% BLOCKED
2SAV
322.8SAV
0MGOROACHES INSIDE THE MH.
337.8FL
319TFDOPEN, 20% BLOCKED
340.9MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK

Properties (5)

additional_info
RFIR INSPECTION
custom_field_three
BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-08-18T08:50:05-07:00