08 0465_08 0464_8152016_021909.mp4
2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN & MISSING AREAS MISSING TILES CIRCUM&LONG
2 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR
2 ft. - General Observation - 100% MISSING TILES START 10:00 TO 2:00
2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEWVERE AGG SREAS MISSING TILES
8.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM
16 ft. - General Observation - 50% MISSING TILES START
32.4 ft. - General Observation - 100% MISSING TILES START
43.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRISON BEYOUND REBAR
43.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR
55.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR CIRCUM
62.5 ft. - General Observation - MISSING TILES 30%
76.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR
84.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR
90.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR
95.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CRRROSION BEYOUND REBAR
99.1 ft. - General Photograph
104.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO
109.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR
113.7 ft. - Surface Reinforcement Corroded, at 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR
131.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES
134.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO
146 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO
154.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR CORRODED BEYOUND REBAR
163.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES
197.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO
218.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES
229 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO
233.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO
256.5 ft. - General Observation - FEW TILES
272.9 ft. - Surface Missing Wall, at 02 o'clock, within 8 inches of joint: NO - 3" X3" SOIL VISIBLE
272.9 ft. - General Photograph - SOIL VISIBLE
324 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO
354 ft. - General Observation - FEW TILES IN PLACE
415.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO
418.7 ft. - General Photograph
476.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES
| Distance | Code | Observation |
|---|---|---|
| 498.2 | SRC | BROKEN MISSING REBAR CIRCUM &LONG |
| 43.2 | SRC | CORRISON BEYOUND REBAR |
| 354 | TF | Active |
| 2 | SRC | BROKEN & MISSING AREAS MISSING TILES CIRCUM&LONG |
| 2 | SRC | LONG REBAR |
| 0 | AMH | 2:10AM |
| 0 | MGO | Conn. @ Mh, 3 O' Clock. Active |
| 99.1 | MGP | — |
| 0 | MWL | — |
| 2 | MGO | 100% MISSING TILES START 10:00 TO 2:00 |
| 272.9 | SMW | 3" X3" SOIL VISIBLE |
| 154.5 | SRC | MISSING REBAR CORRODED BEYOUND REBAR |
| 218.1 | SRC | — |
| 131.5 | SRC | — |
| 32.4 | MGO | 100% MISSING TILES START |
| 95.9 | SRC | CRRROSION BEYOUND REBAR |
| 498.2 | MGO | Conn. @ Mh, 12 O' Clock. Capped |
| 256.5 | MGO | FEW TILES |
| 476.3 | SRC | — |
| 272.9 | MGP | SOIL VISIBLE |
| 324 | SRC | — |
| 8.8 | SRC | CIRCUM |
| 415.7 | SRC | — |
| 498.2 | MGO | Conn. @ Mh, 9 O' Clock. Active |
| 113.7 | SRC | BROKEN REBAR |
| 233.8 | SRC | — |
| 374.1 | MGO | FEW TILES IN PLACE |
| 16 | MGO | 50% MISSING TILES START |
| 43.2 | SRC | BROKEN MISSING REBAR |
| 146 | SRC | — |
| 2 | SAM | SEWVERE AGG SREAS MISSING TILES |
| 498.2 | SRC | CORRODED BEYOUND REBAR |
| 354 | MGO | FEW TILES IN PLACE |
| 498.7 | AMH | 3:45AM |
| 163.3 | SRC | — |
| 498.2 | SAM | SEVERE AGG |
| 84.3 | SRC | MISSING REBAR |
| 229 | SRC | — |
| 498.2 | SRC | LONG REBAR |
| 104.3 | SRC | — |
| 62.5 | MGO | MISSING TILES 30% |
| 300.2 | TF | Open |
| 76.5 | SRC | BROKEN MISSING REBAR |
| 8 | TF | Open |
| 197.1 | SRC | — |
| 418.7 | MGP | — |
| 109.2 | SRC | CORRODED BEYOUND REBAR |
| 55.9 | SRC | MISSING REBAR CIRCUM |
| 134.8 | SRC | — |
| 272.3 | TF | Active |
| 90.9 | SRC | BROKEN MISSING REBAR |
| 0 | MWM | — |