Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2016, 09:46 AM
  • 08 0131_08 0130_7272016_025455.mp4

Date
07/27/2016
W/O
0574374
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00006
PipeID
P00187
Time
2:46 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0207
Sewer Name
08 FIGUEROA STREET TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
20160723MDM_FIGUEROA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0131
Downstream MH
08 0130
Dir. of Survey
Downstream
Length Surveyed
277.7 ft.
Total Length
277.7 ft.
Structural Index
2
Structural Quick
3127
Structural Rating
17
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
17
Pipe schematic from manhole 08 0131 to 08 0130
MH: 08 0131MH: 08 0130downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:55AM0 ft. MWL - Water Level, 2 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped6.7 ft. MGO - General Observation - 12" VCP41.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT58.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active110.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped120.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE152.7 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H162.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped184.1 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SLIGHT209.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active219.5 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT260.6 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT261.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open263 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT266.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H277.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped277.7 ft. AMH - Downstream Manhole, Survey Ends - 3:25AM

Observation photos (1)

  • General Observation - 12" VCP

    6.7 ft. - General Observation - 12" VCP

Observations (20)

DistanceCodeObservation
0AMH2:55AM
0MWL
120.1FCHAIRLINE
0MWM
277.2MGOConn. @ Mh, 3 O' Clock. Capped
209.3TFActive
41.8FCSLIGHT
184.1FCSLIGHT
277.7AMH3:25AM
162.1TFCCapped
6.7MGO12" VCP
110.4TFCCapped
152.7FCH
263FCSLIGHT
260.6FCSLIGHT
266.9FLH
0MGOConn. @ Mh, 3 O' Clock. Capped
261.1TFOpen
58.9TFActive
219.5FCSLIGHT

Properties (4)

custom_field_three
FEW SLIGHT FRACTURES
custom_field_two
4
customer
LACSD
datetime
2016-07-27T02:46:04-07:00