Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2016, 09:01 AM
  • 08 0132_08 0131_7272016_020837.mp4

Date
07/27/2016
W/O
0574374
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00006
PipeID
P00188
Time
2:01 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0207
Sewer Name
08 FIGUEROA STREET TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
20160723MDM_FIGUEROA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0132
Downstream MH
08 0131
Dir. of Survey
Downstream
Length Surveyed
286.7 ft.
Total Length
286.7 ft.
Structural Index
2
Structural Quick
332A
Structural Rating
30
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
30
Pipe schematic from manhole 08 0132 to 08 0131
MH: 08 0132MH: 08 0131downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 0 %of cross sectional area - NO FLOW8 ft. MGO - General Observation - 12" VCP19.2 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE20.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped26.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES58.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT70.9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE70.9 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SLIGHT71.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active71.6 ft. MWL - Water Level, 2 %of cross sectional area123.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped137.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - HAIRLINE137.1 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE170.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped189.1 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE200.7 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H222 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped224.1 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H232.7 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H240.8 ft. CC - Crack Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES244.2 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H248.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H273.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped286.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped286.7 ft. AMH - Downstream Manhole, Survey Ends - 2:45AM

Observation photos (1)

  • General Observation - 12" VCP

    8 ft. - General Observation - 12" VCP

Observations (27)

DistanceCodeObservation
273.8TFCCapped
232.7FCH
58.3FLSLIGHT
70.9FCHAIRLINE
8MGO12" VCP
20.2TFCCapped
0AMH2:10AM
170.7TFCCapped
26.1CL
222TFCCapped
19.2FCHAIRLINE
189.1FCHAIRLINE
137.1FLHAIRLINE
240.8CC
248.4FCH
0MWM
286.7AMH2:45AM
71.6TFActive
244.2FCH
224.1FCH
70.9FCSLIGHT
0MWLNO FLOW
137.1FCHAIRLINE
286.3MGOConn. @ Mh, 3 O' Clock. Capped
71.6MWL
123.5TFCCapped
200.7FLH

Properties (4)

custom_field_three
FEW SLIGHT FRACTURES
custom_field_two
4
customer
LACSD
datetime
2016-07-27T02:01:30-07:00